MOUNTING / MOUNTING WITH HOUSING FOOT B3
9/29
MB245EN - 11171693, 19A3, Baumer_PMG10-SSI_II_EN
4.2
Mounting with housing foot B3
4.2.1
Mounting the spring disk coupling to the device
We recommend using the Baumer Hübner spring disk coupling K 35, see
, available as accessory� When other couplings are used pay attention to
manufacturer‘s notes�
4.2.2
Mounting to drive shaft
)
Service life restrictions and angle error by runouts
High runout of the drive shaft can cause device angle error�
High runout of the drive shaft can cause vibrations, which can shorten the ser-
vice life of the device�
» Lubricate drive shaft!
» Minimize drive shaft runout (≤0.2 mm; ≤0.03 mm recommended).
i
The device must be mounted with cable connection facing downward and not
exposed to water�
M
t
= 1 Nm
2�5 mm