7
|
Functions
Baumer
42
Operating Manual
DAB10, DST53, DST76 | V3
7.3.5
Parameterization of the SSCx switching functions
With the SSC, several switching functions can be set depending on the current process value.
For the parameterization of the SSC the following must be defined:
n
Mode (single point/window/two point)
n
Setpoints (1 or 2 setpoints, depending on the mode)
n
Logic (inversion of the signal)
n
Hysteresis
n
Timing
IO-Link parameter: parameterization of the switching functions (SSCx Settings/SSCx
Hysteresis)
Parameter designation
Description
Settings.SSCx Mode
Select the switching behavior of SSCx:
n
Single Point
n
Window
n
Two Point
Settings.SSCx Setpoint 1
Definition of the process value at which SSCx is set to
enabled.
Settings.SSCx Setpoint 2
Definition of the process value at which SSCx is set to
disabled (for the modes
Window
and
Two Point
).
Settings.SSCx Logic
Logic of SSCx:
n
Normal
n
Inverted
Hysteresis.SSCx Alignment Mode
Selection of the hysteresis alignment (for the modes
Sin-
gle Point
and
Window
).
Hysteresis.SSCx Width
Definition of the hysteresis width.
Hysteresis.SSCx.Width Mode
Define the scale of the hysteresis width of SSCx. The
width can be stated as an absolute value in the unit of
the process factor (e.g. 10 N).
Содержание DAB10