Baumer
Functions
|
7
V3 | DAB10, DST53, DST76
Operating Manual
31
7.3.1.3
Teaching in the sensor characteristics via the teach-in process
In addition to the manual parameterization of the sensor characteristics, you can also carry out
the parameterization via a teach-in process:
n
Offset teach-in (
Teach-In Offset/Taring
)
n
Key value teach-in (
Teach-In Sensitivity
)
During the teaching-in process, the amplifier electronics superimpose the filter
Moving Average
over the input signal. The filter increases the precision for measuring the input signal.
7.3.1.3.1 Offset teach-in (Teach-In Offset/Taring)
With the
Teach-In Offset/Taring
function you can tare the sensor. Carry out the offset teach-in
after installation and ideally following several cycles at full load. The following options are avail-
able to you for the offset teach-in:
n
Via IO-Link (cyclic data)
n
Via one of the two I/O pins. In the factory settings SIO2 (DQ/DI connection) is assigned with
this function.
Example 1: Offset teach-in without pre-load
Characteristics of the sensor:
n
Nominal process value: 1000 N
n
Key value: 1.511 mV/V
n
Output signal in an unloaded state: 0.2 mV/V
Enter the nominal process value and the key value under
Parameter
|
Customer Sensor Ad-
justment
. The activation of
Teach-In Offset
under
Process Data
|
PDO
initiates the offset
teach-in. Subsequently, the value 0.2 is displayed under
Parameter
|
Offset
.
Example 2: Offset teach-in with pre-load
Characteristics of the sensor:
n
Nominal process value: 1000 N
n
Key value: 1.511 mV/V
n
Pre-load (sensor in a loaded state): 200 N
n
Output signal with pre-load: 0.502 mV/V
Enter the nominal process value and the key value under
Parameter
|
Customer Sensor Ad-
justment
. Now enter the pre-load 200 N in the parameter
Teach-in.Offset Process Value
. With
the above key value, 200 N result in a signal of 0.302 mV/V. Deducting this value from
0.502 mV/V results in the actual offset of 0.2 mV/V no-load. The activation of
Teach-In Offset
under
Process Data
|
PDO
initiates the offset teach-in. Subsequently, the value 0.2 is displayed
under
Parameter
|
Offset
.
Содержание DAB10