Commissioning
|
7
OM20/ OM30 RS485 with Modbus RTU | V1
Operating Manual
23
The following data (hexadecimal) is read out for the distance value:
n
202 = 7C37
n
203 = 428B
The distance value is divided between 2 Modbus registers (Little Endian). Thus, the less signifi-
cant bits are located at the smaller address, in this case 202. The more significant bits are lo-
cated at the larger address, in this case 203. The distance value must therefore be evaluated as
42 8B 7C 37. This results in a distance of 69.743 mm.
7.3
Measured value and additional information
The measured value and additional information can be called up by calling up the input register
with the address 200.
Modbus RTU command – input register: measured value and additional information
Address 200 – All Measurement Values:
Address
Access
Number of
registers
Data type
Description
200
Read
1
unit16_t
Measured value signal quality:
n
0 = ok
n
1 = weak signal
n
2 = critical signal
201
Read
1
unit16_t
Bit 0: switching output:
n
0 = inactive
n
1 = active
Bit 1: alarm output
n
0 = inactive
n
1 = active
202 - 203
Read
2
float32_t
Distance [mm]
204 - 205
Read
2
float32_t
Measurement rate [Hz]
206
Read
1
unit16_t
Exposure reserve
207 - 208
Read
2
unit32_t
Response delay [µs]
209 - 210
Read
2
unit32_t
Time stamp [s]
211 - 212
Read
2
unit32_t
Time stamp [µs]
INFO
The distance value in address 202 and 203 can also be read individually. For this, read out reg-
ister 202 with register number 2. A single readout of the distance can reduce the transmission
time.