OPTIM ALPHA ELECTRIC 1100 HEATED TOWEL RAIL 

 
INSTALLATION INSTRUCTIONS 

For use with electric supply only. This cannot be used as a dual source towel rail connected to 
the central heating system. 
 

Position: 

This electric towel rail is intended to be installed in a bathroom or shower-room. It is IP54 rated 
and may be wall-mounted in the Zone 2 area (see Fig below), but the electrical connection box 
must be outside the Zone 2 area.  Its position must be such that the thermostat control cannot 
be reached by a person in the bath or shower. 
 

 

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
Fixing to the wall: 

Follow the instructions on pages 3 and 4. 
The  fixings  supplied  are  suitable  for  use  in  solid  masonry.  Use  a  10mm  bit  for  the  wall  plugs 
supplied. The wall must be strong enough to support the weight of the towel rail. For any other 
wall types you will need to source appropriate fixings. If fitting to a plasterboard wall either utilise 
the noggins, or otherwise strengthen do not fix through plasterboard alone. 
 

Electrical connection: 

The towel rail is supplied complete with its own mains cable. Do not use an extension cable. It is 
a 3-wire product which must be earthed. It should be connected to the household fixed wiring by 
a  qualified  electrician  in  accordance  with  the  national  Wiring  Regulations  (BS.7671).  A  switch 
for disconnection from the electricity supply, having a contact separation in all poles that provide 
full  disconnection  under  overvoltage  category  III  conditions,  must  be  incorporated  in  the  fixed 
wiring. A switched spur outlet incorporating a 3A fuse may be used, but this must be positioned 
outside  the  Zone  2  area  (i.e.  further  away  from  the  bath  or  shower).  The  national  Wiring 
Regulations also require that each circuit supplying a bathroom must be protected by a 30mA 
RCD in its supply.  

 
 
 
 

Zone 1

Zone 2

Zone 0

225c

m

Zone 1

60cm

1) Side view, bath

2) Top view

3) Side view, shower

Zone 1

Zone 2

225c

m

60cm

Zone 1

Zone 0

Zone 2

60cm

60cm

Zone 0