Installation Instructions 

 

 

Issue Date  December 10, 2019 

 

H17 Series BASO® Automatic Pilot Valve 

©  2019 BASO Gas Products

 

1

 

  Part No. BASO-INS-H17, Rev. C 

www.baso.com 

H17 Series BASO® Automatic Pilot Valve 

 

Application 

The H17 Series pilot valves provide complete shutoff 
in the event that the flame heating the thermocouple is 
extinguished. Applications include room heaters, 
infrared heaters, salamanders, and refrigerators. 

H17 models are also available with a higher ambient 
temperature, up to a maximum of 300

F (150

C), for 

use on commercial ovens, broilers, and other 
applications. 

IMPORTANT: 

Only qualified personnel should 

install or service BASO® Gas Products. These 
instructions are a guide for such personnel. Carefully 
follow all instructions in this document and all 
instructions for the appliance. 

 

IMPORTANT: 

Make all gas installations in 

accordance with applicable local, national, and 
regional regulations. 

 

!

  CAUTION:  Risk of Electric Shock. 

Disconnect power supply before making electrical 
connections to avoid electric shock. 

 

Note: 

In applications that do not require electrical 

power, disregard the above caution. 

!

  WARNING: Risk of Explosion or Fire. 

Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the H17. Failure 
to shut off the gas supply can result in the release of 
gas during installation or servicing, which can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 

 

IMPORTANT: 

Verify that the valve is installed 

only in applications where the specified maximum 
ambient (surface) temperature and maximum 
operating pressures do not exceed the limits in the 

Technical Specifications

 section. 

 

To install the H17 valve: 

1. 

Shut off power to the appliance (if applicable). 

2. 

Shut off the gas at the main manual shutoff valve. 

3. 

Ensure that the gas flows through the valve body 
in the direction indicated by the arrow on the 
valve body. If the valve is installed with the gas 
flow in the opposite direction of the arrow, 
leakage can occur. 

IMPORTANT: 

Do not use a wrench on any 

surface other than the casting flats provided at the 
inlet and outlet ends of the valve body. The H17 may 
be damaged in the mounting process if a wrench is 
used on any other surface. Using a wrench 
incorrectly may void the warranty. 

4. 

Mount the valve to the pipework. The H17 valve 
may be mounted in any convenient position. Use 
an approved pipe joint sealing compound on the 
male threads before assembly. Remove excess 
compound after mounting the valve to the 
pipework. Threads of the pipe and nipples must 
be smooth and free of tears and burrs. Steam 
clean all piping to remove foreign substances 
such as cutting oil or thread chips. A sediment 
trap should also be installed in accordance with 
the National Fuel Gas Code (ANSI Z223.1). See 
Figure 1. 

5. 

Attach the thermocouple securely to the pilot 
burner, and screw the terminal end to the 
BASO® power unit terminal on the valve. Make 
sure this connection is clean. Tighten the 
thermocouple lead nut finger tight plus a 
maximum of 1/8 turn. Do not overtighten. 

Содержание H17 Series

Страница 1: ...njury or death IMPORTANT Verify that the valve is installed only in applications where the specified maximum ambient surface temperature and maximum operating pressures do not exceed the limits in the Technical Specifications section To install the H17 valve 1 Shut off power to the appliance if applicable 2 Shut off the gas at the main manual shutoff valve 3 Ensure that the gas flows through the v...

Страница 2: ...the main manual shutoff valve and open the pressure connection between the manual shutoff valve and the H17 valve b Connect air tubing with a maximum pressure of 1 1 2 times the valve s maximum operating pressure as indicated on the valve to the opened pressure connection c Paint all pipe and pilot tube connections with a rich soap and water solution If bubbles occur this is an indication of a lea...

Страница 3: ...setting The main burner ignites from the pilot burner 5 Set the thermostat to the lowest setting The main burner will extinguish 6 Extinguish all flames by closing the manual shutoff valve Verify that the valve drops out within 90 seconds 7 Relight the pilot burner or main burner in required applications 8 Check the millivoltage output of the thermocouple and milliampere dropout range at the BASO ...

Страница 4: ...m K19 18 to 72 in 457 to 1 830 mm Inlet Outlet Pipe Size 1 8 1 4 3 8 and 1 2 in NPT Types of Gas Natural Liquefied Petroleum LP or LP gas air mixtures Packaging Bulk pack supplied to original equipment manufacturer individual pack optional Bulk Pack Quantity 60 Bulk Pack Weight 27 lb 12 kg Agency Listing CSA AGA CGA Certificate Number 229521 1656088 UL File Number MH2926 H17AA BA and CA only Speci...

Отзывы: