Basler SR6A Скачать руководство пользователя страница 31

Sequence of Operation (Parallel) 

The following instructions describe the procedures to be followed for paralleling generators on an isolated 

bus. These procedures should be completely reviewed and understood before paralleling is attempted. 
a.  Start generator set #1. 
b.  Close the circuit breaker to connect the generator to the bus. 
c.  Adjust the voltage and frequency of generator set #1 to nominal. 
d.  Apply load. If possible, load should be 10% or more of its kW rating. 
e.  Start generator set #2. 
f.  Adjust the voltage of the generator to nominal. 
g.  Adjust the speed of generator set #2 slightly higher than that of generator set #1. 
h.  Observing the synchroscope (or lights), close the circuit breaker (generator set #2) when the set is in 

phase with generator set #1. 

i.  Immediately after closing the breaker, verify the indication on the ammeter for generator set #2. They 

should read well within the rating of the generator. If they do not, stop the system and refer to the 

Troubleshooting

 chapter. If unstable operation is indicated, see 

Parallel Operation

 above. If operation 

is stable, see the next step. 

j.  Adjust the speed of generator set #2 to the point where each set is carrying the desired share of kW 

load. 

k.  Adjust the voltage of generator set #2 until the ammeter reading of both sets is near minimum. 
l.  If kvar or power factor meters are available, adjust the voltage-adjust rheostat for equal or 

proportional kvar or power factor reading. 

m.  If the sets are equipped with power factor meters instead of kW meters, alternately adjust the speed 

and voltage on generator set #2 until the ammeter readings are proportional and the power factor 

readings are equal. 

 

Note 

To obtain the best results, final adjustments should be made with full 

load on the bus.

 

n.  With full load applied, readjust the speed and voltage on generator set #2 until the desired load 

division is obtained. 

The best adjustment is obtained when both sets are supplying the same percent of rated current, the kW 

(or power factor) readings are equal, or the sum of the ammeter currents of the two sets is minimum. 
Upon closing the circuit breaker for generator set #2 (

Sequence of Operation

 above), improper operation 

may result. This condition may be accompanied by a very high ammeter reading, the circuit  breaker may 

open due to current overload, or it may be opened by the reverse power relay. In order to isolate this 

problem to the faulty speed or voltage regulating system, perform the following steps: 
a.  Parallel the generators as instructed in 

Sequence of Operation

, steps a through h. 

b.  Immediately after closing the circuit breaker, observe the kW and kvar, or power factor meters. The 

following conditions may occur: 

1.  A high ammeter reading accompanied by a large kW unbalance. When this condition 

exists, the speed regulating system is faulty. 

2.  A high ammeter reading accompanied by a kvar or power factor unbalance but a 

constant kW. When this condition exists, the voltage regulating system is faulty. 

Another method of isolating the preceding trouble is to parallel the generators using manual voltage 

control (if available). If proper operation is obtained, the voltage regulating system may be at fault. 

 

 

CALL US TODAY 

1-888-POWER-58

REQUEST A QUOTE 

[email protected]

SHOP ONLINE 

www.genpowerusa.com

CALL US TODAY 

1-888-POWER-58

REQUEST A QUOTE 

[email protected]

SHOP ONLINE 

www.genpowerusa.com

Содержание SR6A

Страница 1: ...Number 9017700XXX Publication 9017700991 Revision J Jul 13 CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUO...

Страница 2: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 3: ...ng caution and note boxes Each type is illustrated and defined as follows Warning Warning boxes call attention to conditions or actions that may cause personal injury or death Caution Caution boxes ca...

Страница 4: ...Terms of Products and Services document available at www basler com terms This publication contains confidential information of Basler Electric Company an Illinois corporation It is loaned for confid...

Страница 5: ...order Manual Revision and Date Change J Jul 13 Converted manual into new style and structure I This revision letter not used A through H No data available Nov 75 Initial release CALL US TODAY 1 888 PO...

Страница 6: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 7: ...s Terminal A 13 Input Power Terminals 3 and 4 13 Parallel Compensation Terminals 1 and 2 14 Reactive Droop Compensation Droop 14 Reactive Differential Compensation Cross Current 14 Wiring 18 Operation...

Страница 8: ...29 Poor Voltage Stability 30 Voltage Recovers Slowly with Load Change 31 Parallel Generators Do Not Divide Real Power Load Equally 31 No Reactive Droop Compensation Can Be Obtained for Parallel Gener...

Страница 9: ...nsation 5 A at 25 VA Droop Adjustment to 6 Power Input SR6A 120 Vac 10 400 Hz 840 VA SR9A 240 Vac 10 400 Hz 1 680 VA If correct voltage is not available for power input a suitable power transformer mu...

Страница 10: ...act the factory for additional variations Parallel compensation Voltage build up relay Single or three phase sensing Sensing voltage Cover Voltage adjust rheostat Type of stability circuit Accessories...

Страница 11: ...range will occur Model and Style Number Description SR6A and SR9A electrical characteristics and operational features are defined by a combination of letters and numbers that make up the style number...

Страница 12: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 13: ...ew cycles after load application A short circuit on the generator output could reduce the voltage from the generator to zero Either of these conditions can cause reduction of the available field power...

Страница 14: ...enerator output voltage When a lagging power inductive load is applied to the generator the voltage across R25 becomes more in phase with the sensing voltage and the combined vectors of the two voltag...

Страница 15: ...ive differential compensation cannot be used when paralleled with the utility or other infinite utility bus When reactive differential compensation is to be used on an isolated bus that may parallel w...

Страница 16: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 17: ...emperature does not exceed its operational limits Due to its rugged construction the regulator can be mounted directly on the generator Outline dimensions are shown in Figure 3 Figure 3 Outline Drawin...

Страница 18: ...in Figure 4 Figure 4 Outline Drawing Voltage Adjust Rheostat Basler P N 03456 CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 PO...

Страница 19: ...ion The SR6A SR9A Voltage Regulators are factory preset for 120 Vac sensing The voltage regulator contains an internal sensing transformer s T1 T2 provided with taps for various input sensing voltages...

Страница 20: ...al labeled with the desired sensing voltage Step 6 For three phase sensing units move the wire at terminal T1 120 to the T1 terminal labeled with the desired sensing voltage Also move the wire from te...

Страница 21: ...shown in Figure 7 If these polarities are not known the system should be operated on manual voltage control and the polarities accurately determined before connecting the voltage regulator into the s...

Страница 22: ...ge drop is not objectionable Reactive Differential Compensation Cross Current On parallel reactive differential compensation applications a contact should be used to short the paralleling CT secondary...

Страница 23: ...Brush Type Rotary Exciter CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ON...

Страница 24: ...s Rotary Exciter or Static Exciter CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com...

Страница 25: ...ies are shown A B C phase rotation Figure 9 Reactive Differential Cross Current Compensation CT s Interconnection CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www gen...

Страница 26: ...n Figure 10 Figure 10 Internal Wiring Diagram CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genp...

Страница 27: ...be temporarily installed for initial operation Caution When used this switch must always be installed in the input power line to the regulator terminal 3 or 4 Do not install this switch in the dc fiel...

Страница 28: ...hould be completely reviewed and understood before system operation is attempted Also locating controls and adjustments pertinent to system operation would be beneficial Single Unit Operation No Load...

Страница 29: ...e cause of generator voltage instability If a stability problem still exists after performing the procedure in Single Unit Operation f and g above a thorough check of the governor should be made Field...

Страница 30: ...features function properly The following test may be used a Place each set in operation in accordance with Initial Operation Single Unit Operation earlier in this chapter b Verify that the paralleling...

Страница 31: ...er readings are proportional and the power factor readings are equal Note To obtain the best results final adjustments should be made with full load on the bus n With full load applied readjust the sp...

Страница 32: ...and voltage regulator causes paralleling problems that cannot be isolated using manual control CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL U...

Страница 33: ...from the date of shipment from Basler Electric Units submitted for warranty repair should be returned to Basler Electric freight prepaid with complete description of the installation and the reported...

Страница 34: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 35: ...ltage is correct proceed to Step 6 Step 6 Verify that the generator output is neither shorted nor overloaded If the generator output is shorted remove the short and repair the wiring If the generator...

Страница 36: ...external Voltage Adjust Potentiometer R1 If the Voltage Adjust Potentiometer is shorted replace the Voltage Adjust Potentiometer If the Voltage Adjust Potentiometer is not shorted proceed to Step 4 S...

Страница 37: ...Step 2 Check that the Voltage Adjust Potentiometer R3 is not set too low If the Voltage Adjust Potentiometer is set too low adjust the potentiometer If the Voltage Adjust Potentiometer is within limit...

Страница 38: ...load is not unbalanced as the regulator averages all three phases together For single phase sensing proceed to Step 7 If the load is unbalanced balance the load If the load is balanced proceed to Step...

Страница 39: ...setting If R4 is properly adjusted proceed to Step 3 Step 3 Verify that the generator frequency is stable If the frequency is unstable consult with the governor manufacturer If the frequency is stabl...

Страница 40: ...n in the Installation chapter If the CT does provide the required 3 to 5 A secondary current proceed to Step 3 Step 3 Verify that the paralleling CT s polarity is correct If the CT s polarity is incor...

Страница 41: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Страница 42: ...CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com CALL US TODAY 1 888 POWER 58 REQUEST A QUOTE parts genpowerusa com SHOP ONLINE www genpowerusa com...

Отзывы: