BE1-MMS100 

MULTIFUNCTION 

METERING SYSTEM 

The BE1-MMS1 00 is an economical, microprocessor based, multifunction 

revenue-accurate power metering system that provides multifunction revenue­
accurate power metering, contact status monitoring, and output control func­
tions in an integrated system. 

ADVANTAGES 

• 

Provides accurate metering of voltage, current, Watts, VARs, and bi-direc-

tional energy measurements. 

• 

Measures individual and total harmonic distortion up to the 31st harmonic. 

• 

Monitors discrete inputs from utility kWh pulse initiators. 

• 

Stores Minimum and Maximum Energy Values. 

• 

Stores 36 days* of 15 minute average data for Volts, Amps, Watts, VARs, 
Power Factor,  frequency and accumulated pulse counts, plus values for 
imported, exported and total kWh,  kVARh, and kVAh, and elapsed time since 
last reset or it stores 12 oscillographic records* of 21  cycles each at 64 
samples per cycle. 

• 

Monitors the status of input contacts from  breakers,  targets,  switches,  etc. 

• 

Provides control outputs through built-in interposing relays. 

• 

Available in fully drawout half rack case. Two Basler Electric half rack lEOs 

(Intelligent Electronic Devices) can be dovetailed together to mount in a 

standard 19-inch equipment rack with no special mounting hardware. 

History is limited to  18 days or oscillography is limited to 6 events for the  DNP 3.0 option. 

WINDOWS® SOFTWARE 

Interface for setting  and communicating with Basler metering  products. 
Request  BESTCOMS  for  BE1-MMS100. 

ADDITIONAL  INFORMATION 

INSTRUCTION  MANUAL 

Request publication 9326700991 

UMOS''  SOFTWARE  BULLETIN 

Request publication LAB 

MODBUS  INSTRUCTION  MANUAL 

Request publication 9326700993 

DNP  INSTRUCTION  MANUAL 

Request publication 9326700992 

§

.Basler  Electric 

P.  0.  BOX 269 HIGHLAND,  ILLINOIS,  U.S.A. 62249  PHONE 618·654·2341  FAX 618·654·2351 

FEATURES 

Page  2 

APPLICATIONS 

Pages  2-3 

FUNCTIONAL 

DESCRIPTION 

Pages  3-8 

SPECIFICATIONS 

Pages  9-10 

ORDERING 

INFORMATION 

Page  11 

LAD-5 

7-01 

www 

. ElectricalPartManuals 

. com 

Содержание BE1-MMS100

Страница 1: ...ors the status of input contacts from breakers targets switches etc Provides control outputs through built in interposing relays Available in fully drawout half rack case Two Basler Electric half rack...

Страница 2: ...ng chips Integral HMI with 2x16 character display Wide range ac dc power supply options provide long holdup time to ride through dips on ac power source 1OOms with four output relays energized upon co...

Страница 3: ...ied from 67 or 120Vac PTs 1 2 3 or 4 ac currents supplied from 1A or 5A CTs specified at time of order Meter input signals are supplied from PTs and CTs as paired sets of input signals Input signals a...

Страница 4: ...the status input channels total of four channels available Pulse repetition rates of up to 20 per second on each channel are acceptable Inputs are scanned at 10 millisecond intervals A debouncing algo...

Страница 5: ...y 48 125V AC DC Serial Number XXXXXXXXXX Unit Freeze Power Status Rx Tx Display 0 0 0 0 0 BE1 MMS COM RS 232 Figure 1 Front p anel of BE1 MMS100 LCD DISPLAY USAGE The LCD display is a 16 character by...

Страница 6: ...e Configuration Circuit Active Analog CT Filter Circuit Circuit ISO l ISO f ISO l ISO l Power Supply Flash Memory Ground o Chassis HMI AID LCD Circuit Display Keypad ISO ISO Microprocessor r 1 ISO I W...

Страница 7: ...N1 BUS A B c N IN2 IN3 IN4 IRIG PWR GND IN4 IRIG 1 BREAKER I I I I I 07 05 03 01 A 66Jv B2 w 3 B4 v 5 B6 7 sa y y y y ISO ISO ISO ISO I Oelta Wye I A B C N LINE 7 IN IC IB 71A Configuration Circuit LJ...

Страница 8: ...elay Contacts Chan 1 Output Relay Contacts Chan 2 Output Relay Contacts Chan 3 Output Relay Contacts Chan 4 Output Relay Contacts Chan 5 Output Relay Contacts Chan 6 Total Harmonic Distortion Ph a Tot...

Страница 9: ...WER SUPPLY Option 1 64 cycle adjusted to input frequency 10 75Hz DC range 35 150V AC range 55 135V Option 2 Option 3 Burden OUTPUT CONTACTS Contact Current 30 Amps 10 Amps 0 3 Amps 10 Amps Operating V...

Страница 10: ...vironmentalTestProcedures Part 2 Test Z AD Composite Temperature Humidity Cyclic Test Note LCD Display is inoperative below 20 C VIBRATIONI SEISMIC Qualified to IEC255 21 1 Class 1 SHOCK Qualified to...

Страница 11: ...ower supply H Half rack case 3 DNP 3 0 communications jBE1 MMS100 I 1 Amp Nominal Systems 3 3 phase sensing B 1 Amp Independent Gnd Input 5 Amp Nominal Systems E 5 Amp Independent Gnd Input STANDARDAC...

Страница 12: ...ND ILLINOIS U S A 62249 PAE Les Pins 67319 Wasselonne Cedex FRANCE PHONE 618 654 2341 FAX 618 654 2351 PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http www basler com info basler com Printed in U S A w...

Отзывы: