10-10
Human-Machine Interface
BE1-951
Figure 10-9. Virtual Control Switch 143 Screen
HMI OPERATIONS
The following paragraphs describe how the HMI is used to set and control relay functions.
Entering Settings
Settings for protection functions can be edited at menu branch 5,
PROTECTION LOGIC of the HMI LCD.
Settings for general and reporting functions can be edited from menu branch 6,
GENERAL SETTINGS. To
edit a setting using the manual scrolling pushbuttons, perform the following procedures.
1.
Scroll to the screen that displays the function to be edited.
2.
Press the EDIT pushbutton to gain access. If password security has been initiated for settings, you will
be prompted to enter the appropriate password. See the paragraphs,
Entering Passwords, for details
on entering passwords from the HMI. Once access has been gained, the EDIT LED will be lighted and
a cursor will appear in the first settings field on the screen.
3.
Press the UP or DOWN scrolling key to select the desired setting. Some settings require entering a
number one character at a time. For example, to enter a 51 pickup as 7.3 amps, you would press the
UP pushbutton until the 7 is showing. Then, press the RIGHT pushbutton to move the cursor over and
press the UP pushbutton until the . is showing. Then, press the RIGHT pushbutton to move the cursor
over and press the UP pushbutton until the 3 is showing. Other settings require scrolling through a list
of selections. For example, you would move the cursor over to the CRV field and then scroll through
a list of available TCC curves.
4.
Once all of the settings on the screen have been entered, press the EDIT pushbutton a second time and
the settings will be validated. If the settings are in range, the screen will flash CHANGES SAVED, and
the EDIT LED will go out. If you want to abort the edit session without changing any settings, press the
RESET pushbutton before you press the edit pushbutton the second time. The screen will flash
CHANGES LOST and the EDIT LED will go out.
Performing Control Operations
Control operations can be executed at menu branch 2,
CONTROL of the HMI LCD. These functions allow
you to control the state of virtual switches, override logic and control the active setting group, and override
the logic and control the state of output contacts. All of these functions work similarly to the process of
entering settings in that you press the EDIT pushbutton, use the UP and DOWN scroll pushbuttons to select
the desired state, and press the EDIT pushbutton for the action to be executed.
Figure 4-3 shows virtual switch 143 as an example of a
virtual switch screen. See Section 4,
Protection And
Control for more details on the x43 and 101 functions.
Table 10-2 describes each of the call-outs shown on
figure 10-9. The user programmable label for this switch
has been set to RCL_DISABL. The TRUE (closed)
state label has been set to DISABLD. And, the FALSE
(open) state label has been set to ENABLED. The
logical mode for this application would be set to Mode
2 (On/Off switch).
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...