BE1-951
Application
8-15
SL-47:0,0
SL-62:0,0,0
SL-162:0,0,0
SL-79:1,VO8,/IN1,VO12,VO9
SL-81:0,0
SL-181:0,0
SL-281:0,0
SL-381:0,0
SL-481:0,0
SL-581:0,0
SL-BF:0,0,0
SL-GROUP:1,0,0,0,0,/0
SL-43:0
SL-143:0
SL-243:0
SL-343:0
SL-101:0
SL-VOA:0
SL-VO1:VO11
SL-VO2:79C
SL-VO3:0
SL-VO4:ALMMIN
SL-VO5:ALMMAJ
SL-VO6:0
SL-VO7:0
SL-VO8:VO11+IN3
SL-VO9:/IN2
SL-VO10:0
SL-VO11:50TPT+50TNT+50TQT+51PT+51NT+51QT
SL-VO12:51PPU+51NPU+51QPU
SL-VO13:0
SL-VO14:0
SL-VO15:0
OC-W-CTL LOGIC SCHEME
Logic scheme OC-W-CTL is intended for use on feeder breakers. This scheme provides overcurrent
protection, breaker failure protection, reclosing, and the control functions required for typical feeders in non-
directional overcurrent protection applications.
In OC-W-CTL, automatic reclosing uses a recluse initiate scheme and is initiated by a protective trip or by
an external recluse initiate (RI) contact.
The components of OC-W-CTL logic are summarized in Tables 8-9, 8-10, 8-11, and 8-12. A diagram of OC-
W-CTL logic is shown in Figure 8-5. Figure 8-6 shows a one-line drawing for the OC-W-CTL logic scheme.
Operation - Control
The virtual breaker control switch (101) is programmed to provide manual trip and close control of the
breaker. Manual breaker control can be achieved by using the front panel HMI or by entering ASCII
commands through the communication ports. Control functions of this logic scheme use both traditional
contact sensing inputs and virtual switches. Virtual switches that are not needed may simply go unused. The
contact sensing inputs can be freed up for other uses by utilizing the virtual switches for other control
functions.
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...