BE1-50 General Information
1-3
Figure 1-3. Style Number Identification Chart
SPECIFICATIONS
Current Sensing
Sensing inputs are nominally rated at 50/60 Hz and have a frequency
range of 40 to 70 Hz. Current ratings and sensing burdens depend on the
sensing range and power supply type (defined by the style number), and
are shown in Table 1-1.
Pickup Range
Continuously adjustable over the range defined by the style number with
independent ranges and adjustments for each phase and neutral pickup.
Pickup Accuracy
±2% or ±40 mA of pickup setting, whichever is greater.
Dropout
Within 2% of pickup.
Timing
1.5 cycles or less from onset of overcurrent condition. (30 milliseconds at
50 Hz, 25 milliseconds at 60 Hz)
Power Supply
Power supply Types F, G, and H derive operating power from the sensing
inputs at a maximum burden of 5 VA per phase at pickup. Externally
powered power supply ratings are shown in Table 1-2.
Содержание BE1-50
Страница 1: ... 05647 6 10 07 14 056 06 0 175 18 4 744 06 4 Publication 9 1710 00 990 Revision C 11 98 ...
Страница 5: ...iv BE1 50 Introduction CONTENTS Continued SECTION 7 MANUAL CHANGE INFORMATION 7 1 Changes 7 1 ...
Страница 12: ...2 2 BE1 50 Human Machine Interface Figure 2 1 Location of Controls and Indicators ...
Страница 20: ...BE1 50 Installation 4 5 Figure 4 7 S1 Case Single Ended Panel Drilling Diagram Rear View ...
Страница 21: ...4 6 BE1 50 Installation Figure 4 8 S1 Case Double Ended Panel Drilling Diagram Rear View ...
Страница 22: ...BE1 50 Installation 4 7 Figure 4 9 Outline Dimensions Rear View ...
Страница 26: ...BE1 50 Installation 4 11 Figure 4 15 Typical Output Connections Sensing Input Type F and Output E or G ...
Страница 29: ...4 14 BE1 50 Installation Figure 4 18 Typical Internal Connections Single Phase Output E Option 3 5 ...