![Basler BE1-50/51B-218 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/basler/be1-50-51b-218/be1-50-51b-218_instruction-manual_2707497045.webp)
9252000995 Rev G
BE1-50/51B-218/-228 Testing
5-3
Test Procedure, Models BE1-50/51B-218 (Five Ampere Sensing Input)
Time Pickup Test
Perform preliminary setup:
•
Connect test setup as shown in Figure 5-1.
•
Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON and SW3-4 to ON.
•
Set TIME DIAL to 0.0.
•
Set CURVE to S
•
Set TIME PICKUP to 0.5.
•
Set INST PICKUP to 90.
Step 1. Slowly increase current to terminals 5 and 6. PICKUP LED should turn RED at a maximum input
current of 0.550 ampere.
Step 2. Decrease input current until PICKUP LED turns GREEN then OFF.
Step 3. Set TIME PICKUP to 2.2.
Step 4. Slowly increase current to terminals 5 and 6. PICKUP LED should change from GREEN to RED
at an input current of 2.131 to 2.269 amperes.
Step 5. Decrease input current until PICKUP LED turns OFF.
INST Pickup Test
Perform preliminary setup:
•
Connect test setup as shown in Figure 5-1.
•
Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON, and SW3-4 ON.
•
Set TIME DIAL to 0.0.
•
Set CURVE to S
•
Set TIME PICKUP to 1.0.
•
Set INST PICKUP to 01.
Step 1. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
0.955 to 1.045 amperes.
Step 2. Decrease input current until INST output contacts open.
Step 3. Set INST PICKUP to 08.
Step 4. Slowly increase current to terminals 5 and 6. INST contacts should close at an input current of
7.815 to 8.185 amperes.
Step 5. Decrease input current until INST output contacts open.
Time Dial Test
Perform preliminary setup:
•
Connect test setup as shown in Figure 5-1.
•
Insure that SW3 switches are set: SW3-1 for the operating frequency, SW3-2 to OFF, SW3-3 to
ON, and SW3-4 ON.
•
Set TIME DIAL to 4.5.
•
Set CURVE to S
•
Set TIME PICKUP to 1.0.
•
Set INST PICKUP to 90.
NOTE
When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect
the calibration of the TIME functions. TIME PICKUP settings of 00 also affect
INST functions.
Содержание BE1-50/51B-218
Страница 2: ......
Страница 6: ...iv BE1 50 51B 218 228 Introduction 9252000995 Rev G This page intentionally left blank ...
Страница 8: ...vi BE1 50 51B 218 228 Introduction 9252000995 Rev G This page intentionally left blank ...
Страница 10: ...ii BE1 50 51B 218 228 General Information 9252000995 Rev G This page intentionally left blank ...
Страница 20: ...1 10 BE1 50 51B 218 228 General Information 9252000995 Rev G This page intentionally left blank ...
Страница 22: ...ii BE1 50 51B 218 228 Controls and Indicators 9252000995 Rev G This page intentionally left blank ...
Страница 24: ...2 2 BE1 50 51B 218 228 Controls and Indicators 9252000995 Rev G P0053 50 SW3 Figure 2 2 Location of SW3 ...
Страница 26: ...2 4 BE1 50 51B 218 228 Controls and Indicators 9252000995 Rev G This page intentionally left blank ...
Страница 28: ...ii BE1 50 51B 218 228 Functional Description 9252000995 Rev G This page intentionally left blank ...
Страница 32: ...ii BE1 50 51B 218 228 Installation 9252000995 Rev G This page intentionally left blank ...
Страница 40: ...4 8 BE1 50 51B 218 228 Installation 9252000995 Rev G This page intentionally left blank ...
Страница 42: ...ii BE1 50 51B 218 228 Testing 9252000995 Rev G This page intentionally left blank ...
Страница 50: ...5 8 BE1 50 51B 218 228 Testing 9252000995 Rev G This page intentionally left blank ...
Страница 52: ...ii BE1 50 51B 218 228 Time Characteristic Curves 9252000995 Rev G This page intentionally left blank ...