9252000994 Rev N
BE1-50/51B-214/-215/-223/-225 Controls and Indicators
2-3
Table 2-1. BE1-50/51B-214/-215/-223/-225 Controls and Indicators (Refer to Figures 2-1 and 2-2)
Locator
Control or Indicator
Function
A
INST MANUAL TRIP
Test Points
When shorted, the test points (jacks) provide a secure means to
manually trip the controlled breaker. Jacks accept a standard 0.08
inch diameter phone tip plug.
B
INST PICKUP
Selectors
Two switches (TENS and UNITS) to select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.
C
Targets
Red target indicators latch when the trip circuit current is greater
than 0.2 amperes. One target each for TIME and INST.
D
TIME PICKUP
Selectors
Two switches (UNITS and TENTHS) to select pickup current in
amperes. Changing switch selectors while the relay is in service
may cause tripping.
E
CURVE Selector
Ten position selector switch to select one of nine inverse functions
or one fixed time function.
F
TIME DIAL Selectors
Two selector switches (UNITS and TENTHS) to select the desired
characteristic curve. A setting of 0.0 results in instantaneous
operation without any intentional delay. A setting of 9.9
corresponds to the typical time provided by an electromechanical
relay at its maximum dial setting.
G
TIME MANUAL TRIP
Test Points
When shorted, the test points provide a secure means to manually
trip the controlled breaker. Jacks accept a standard 0.08 inch
diameter phone tip plug.
H
ACTIVE/PICKUP LED
Red LED indicates sensed current has exceeded the TIME
PICKUP setting. LED turns from red to green when sensed current
falls below 95% of pickup setting. When the LED is green, the
relay is active but has not picked up.
I
Target RESET Button
Linkage extends through back of front cover to reset both gravity
latched target indicators.
SW3
*
SW3-1
SW3-1 selects the system operating frequency. SW3-1 open
(OFF) selects 60 Hz operation. SW3-1 closed (ON) selects 50 Hz
operation.
SW3-2
SW3-2 provides additional time delay for the instantaneous
element. Closing switch SW3-2 (ON) provides an additional
instantaneous delay of 0.1 second.
SW3-3
SW3-3 provides selection of GE IAC type curves or ABB type
curves. Closing switch SW3-3 (ON) selects GE IAC type curves
(refer to Table 1-3). Opening switch SW3-3 (OFF) selects ABB
type curves (refer to Table 1-2).
SW3-4
SW3-4 provides selection of either instantaneous or integrating
reset characteristics. Closing SW3-4 (ON) selects integrating reset
characteristics. Opening SW3-4 (OFF) selects instantaneous reset
characteristics.
*
NOTE: In Revision J and previous relays, switch SW3 is designated as SW8.
Содержание BE1-50/51B-214
Страница 2: ......
Страница 6: ...iv BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...
Страница 8: ...vi BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...
Страница 10: ...ii BE1 50 51B 214 215 223 225 General Information 9252000994 Rev N This page intentionally left blank...
Страница 20: ...1 10 BE1 50 51B 214 215 223 225 General Information 9252000994 Rev N This page intentionally left blank...
Страница 22: ...ii BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N This page intentionally left blank...
Страница 24: ...2 2 BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N Figure 2 2 Location of SW3 P0053 50...
Страница 26: ...2 4 BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N This page intentionally left blank...
Страница 28: ...ii BE1 50 51B 214 215 223 225 Functional Description 9252000994 Rev N This page intentionally left blank...
Страница 32: ...3 4 BE1 50 51B 214 215 223 225 Functional Description 9252000994 Rev N This page intentionally left blank...
Страница 34: ...ii BE1 50 51B 214 215 223 225 Installation 9252000994 Rev N This page intentionally left blank...
Страница 39: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Installation 4 5 Figure 4 4 DC Control Connections BE1 50 51B 215...
Страница 42: ...ii BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...
Страница 52: ...5 10 BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...
Страница 54: ...ii BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N This page intentionally left blank...
Страница 69: ......