![Barth Mini-PLC STG-115 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/barth/mini-plc-stg-115/mini-plc-stg-115_manual_3962499007.webp)
BAR H
Elektronik GmbH
®
7/8
9021-0003-A
23.10.2015
A
Page:
Document:
Date:
Revision:
Mini-PLC
STG-115
Art. No. 0850-0115
MANUAL
© 2014-2015 BARTH Elektronik GmbH | Im Depot 1-3 | D-49838 Lengerich | www.barth-elektronik.de
® BARTH is a registered trademark. All rights reserved.
9021-0003-A
7.1.4 Outputs
Number digital
8+1
Output OUT1 - OUT8
Output type: solid state
I
OUT
<= 1,5 A (resistive load)
@ f
OUT
= 0..100 Hz
U
OUT
>= U
IN
-0,45 V
I
TOT
<= 6 A (paralleling permissible)
Maximal allowable load
inductance for a single switch off
(one output):
V
DD
=12VDC, I
L
=1.5A, Z
L
<=70mH
V
DD
=12VDC, I
L
=1A, Z
L
<=200mH
On-state resistance V
DD
to OUT:
R
ON
<=180mOhm
Turn-on time: t
ON
<=250µs
Turn-off time: t
OFF
<=270µs
Relay output OUT9
Output type: NO/NC changeover
I
NO/NC
<= 1 A (resistive load)
@ f
OUT
= 0..5 Hz
U
NC/NO
<= 30 VDC
Potential isolation
yes
7.1.5 Display
Display Type
STN blue
transmissive negative mode
Backlight
LED, lightguide, white
Display contents
16 x 2 characters
Character pitch
3.55 x 5.95 mm
Character size
2.95 x 5.55 mm
Character font
5 x 8 dots
Dot size
0.55 x 0.65 mm
Operating Temperature
-20 to +70°C
7.1.6 Electrical connection
Electrical Connection
plugable spring terminal
connectors 0.25 to 1.5 mm²
7.1.7 Electromagnetic compatibility (EMC)
Electrostatic discharge
(ESD) on IN1 to IN10
20 kV air discharge
30 kV contact discharge
(IEC/EN 61 000-4-2, level 3)
Electrostatic discharge
(ESD) on OUT1 to OUT9
8 kV (human body model)
(MIL-STD883D)
Electromagnetic fields
Field strength 10 V/m
(IEC/EN 61000-4-3)
7.1.8 Security features
Security Features
Watchdog (WD)
Brown out detection (BOD)
Power up timer (PUT)
7.1.9 Program and data memory
Flash program memory
64 k
cell endurance: 10.000 min
characteristic retention: 40 yrs
EEPROM data memory
1024 byte
byte endurance 100.000 min.
characteristic retention: 40 yrs
7.1.10 Environmental conditions
Operation temperature
-20..+60 °C
(IEC 60068-2-1/2)
Storage temperature
-40..+70 °C
(IEC 60068-2-1/2)
Relative humidity
5 to 95% non-condensing
(IEC 60068-2-30)
Air pressure (in operation)
500 to 1500 hPa
Shock resistance
min. 50 m/s²
(IEC 60068-2-27)
Vibration resistance
min. 25 m/s² @ 10..100 Hz
(IEC 60068-2-6)
Degree of protection
IP 65 (EN 50178, IEC 60529)
(front panel with applied sealing)
Drop
Drop height: 50mm
(IEC 60068-2-31)
Free fall (packaged)
500 mm
(IEC 60068-2-32)
7.1.11 Weight and dimensions
Weight
165 g
(without connectors)
Dimensions
PLC: 110 x 90 x 36 mm (LxWxH)
Cut-out: 68 x 92 mm (LxW)
Hole distance: 100 x 80 mm
Hole diameter: 4.2 mm
Mounting
via four M4 screws
(only cylinder head type)
7.1.12 Ordering information
Ordering information
Mini-PLC
Mini-PLC STG-115
Art. No. 0850-0115
Ordering information
accessory
USB connection cable VK-12
Art. No. 0091-0012