Mounting the Resistance Temperature Device Pt100
Mount the Resistance Temperature Device directly on the
pipe
Mount the Resistance Temperature Device in the lower
area of the pipe cross section
Mount the Resistance Temperature Device at the greatest
possible distance from the heating cable
Fasten Resistance Temperature Device with aluminium ad-
hesive tape if necessary
Installing the End Seal
WARNING
Risk of fire and electric shock from heating cable
Risk of injury due to electric voltage
Mount the end seal on the open end of the heating ca-
ble, commissioning of the junction box is only permit-
ted with the end seal mounted
Cut the trace heater off straight.
Remove the outer jacket on 20 mm.
Remove the exposed grounding braid.
Make sure that the
insulation jacket is not damaged
Cut in a triangle (5 mm) between the bus wires.
CAUTION
The silicone adhesive may cause irritation to skin and
eyes. Avoid eye contact. Avoid repeated or prolonged
skin contact. In case of contact with eyes, rinse with
water and seek medi-cal advice.
Put silicone adhesive onto the exposed insulating jacket
and into the end seal.
Slide the end seal over the end of the trace heater.
NOTICE
Allow the adhesive to cure for 20 minutes, then visu-
ally in-spect. Full strength is reached after 24 hours.