Operation and Installation Manual PBTC-200
21-54C3-7D0001/-
04/2021-EHT-441168
Notice:
Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Page 17 / 45
7
Functional Description
The thermostat module ETM-25Ex-C switches the connected heating load or heating cable on or off by means of a built-in relay. It
switches on when the temperature measured at the Resistance Temperature Device Pt100 is lower than the temperature setpoint. It
switches off if the measured temperature is higher than the set temperature plus hysteresis. The thermostat module switches the
heating load or the heating cable on when the temperature at the Resistance Temperature Device Pt100 falls below the adjusted
temperature set point.
Toggle switch °C / °F is used to switch the temperature unit, 3 rotary coding switches are used to set the temperature setpoint.
The connected Resistance Temperature Device Pt100 measures the actual temperature and ensures the temperature control func-
tion.
In case of a malfunction of the thermostat module or the Resistance Temperature Device Pt100, the thermostat module switches off
the connected heating load or the heating cable.
The electronic thermostat module has a limited service life, which depends on the switching cycles performed. A color and blinking
code of the LED status display indicates the achieved 80% service life. It is an indication that the thermostat module needs to be
replaced. When the 100% service life is reached, the thermostat module switches off the connected heating load or heating cable.
The LED status display shows a further color and blinking code.