![Bartec Ex p Control Unit APEX Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/bartec/ex-p-control-unit-apex/ex-p-control-unit-apex_manual_476017050.webp)
Ex p Control Unit
SIEMENS Set
Operation
Rev. 0
01-37A2-7D0004_SIEMENS_Manual_Exp-Control-Unit_20220216_0_en.docx
Page 49 of 80
Disclaimer: We reserve the right to make technical changes. Changes, errors and printing errors do not justify claims for damages.
Entering parameters
Changing parameters in the web interface must be carried out in a specific order:
Procedure for changing parameters:
Activate the parameter switch.
Log in to the web interface
If you are already logged in, the web interface requires a new log-in
Select the desired parameter
e.g. po – operating pressure 2,5 mbar (250 Pa)
Enter parameter
Enter value 250
Confirm with the “Enter“ key
The following window opens. This is to confirm and check the changed
parameter value.
LED indicators
LED
Colors
Function
p1
Green
Minimum pressure
Lights up when the minimum pressure is
exceeded
p2
Yellow
Pre-alarm
Lights up when the value falls below the set
value
p3
Green
Purge pressure
Lights up during the purge phase and exceeding
of the setpoint value
p4
Red
Maximum pressure
Lights up when the maximum pressure p4 or p5
is exceeded
Operate
Green
Enable / Purge process
Flashes during purge and lights up when enable
given after purge
Status
Green
Supply / Bypass
Lights up when supply voltage is applied and
flashes when bypass activated
Содержание Ex p Control Unit APEX