background image

 

 

   

 

 

Operational Instruction 

(Translation)

 

  Potentiometer 

Type 07-662.-…./…. 

 

 

BARTEC

 GmbH  Max-Eyth-Straße 16  

97980 Bad Mergentheim 

Germany 

Tel.:  +49 7931 597-0 

Fax:  +49 7931 597-119 

[email protected] 

www.bartec.de 

Reservation  Technical data subject to change without notice. Changes, errors and 

misprints may not be used as a basis for any claim for damages. 

EN 1/4 

 

 

 

 

 

 

 

Explosion protection 

 

Technical data 

 

Maximum Ex type of protection 

Depending on the installations; observe the 
specifications on the type label. 

ATEX 

Ex type of protection 

 

  II 2G  Ex d e IIC T6 resp. T5 Gb 

 

  II 2D  Ex tb IIIC T80 °C resp.  

T95 °C Db 

 

0044 

 

Certification 

EPS 14 ATEX 1 696 

IECEx 

Ex type of protection 

 

 

 

Ex d e IIC T6 resp. T5 Gb 

 

 

 

Ex tb IIIC T80 °C resp.  
T95 °C Db 

 

Certification 

IECEx EPS 14.0042 

INMETRO 

Ex type of protection

 

Ex d e IIC T6…T5 Gb 
Ex tb IIIC T80 °C…T95 °C Db 

 

Certification 

NCC 14.02943 

 

Certification 

TC RU C-DE.

ГБ

06.

В

.00443 

Ambient temperature range 

Depending on the installations; observe the 
specifications on the type label.  
 
-20 °C up to max. +70 °C 
(-4 °F up to max. +158 °F) 

Approved for zones 

1, 2 and 21, 22 
 

Electrical data 

Rated voltage: up to 250 V  
Power loss: max. 8 W 

Protection class 

Max. IP 66 (EN 60529) 

Mechanical strength 

Impact energy: max. 7 Nm  

Rotation, electrical/mechanical 

Cemented wire-wound resistors: 

Type 07-662.-.111-….: 

250

 / 270

 

 

Carbon-film resistors on ceramic: 

Type 07-6622-.113-….: 

270

 

 

Precision wire-wound resistors: 

Type 07-6622-.112-….: 

1 turn  
320

 ±2°

 

Type 07-6624-.102-….: 

10 turns  
10 x 360° 
+10° 

Enclosure material 

– 

Stainless steel 

– 

Brass, surface bare/nickel-plated  

Dimensions 

See page 3. 

 

07-6620-7D0002/

A-0

2/

15-STVT-381059

 

Note on instructions 

When working in hazardous areas, the safety of
personnel and equipment depends on compli-
ance with the relevant safety regulations. The
people in charge of installation and mainte-
nance bear a special responsibility. It is essen-
tial that they have an exact knowledge of the
applicable rules and regulations. 
The instructions provide a summary of the most
important safety measures and must be read by
everyone working with the product so that they
will be familiar with the correct handling of the
product. 
The instructions have to be kept for future
reference and must be available throughout the
expected life of the product. 
 

Description 

The type 07-662.-…./…. potentiometer consists
of a metal Ex d enclosure, into which an inser-
tion potentiometer is fitted. 
The metal Ex d enclosures are tailored to the
dimensions of the resistors and will be pro-
duced in different sizes from Ø 30 to 60 mm 
(1.18 to 2.36 in). 
The potentiometer can be fastened and secured
against twisting in a number of ways. Two nuts
are included in each consignment. Optionally
BARTEC provides either threaded holes in the
front panel of the enclosure or an antirotation
pin.  
Accessories, such as rotary and pointer knobs, 
scales, digital drives for 10 turns potentiometer,
and slip clutches could be delivered. 

 

Отзывы: