Commissioning
Ex p control unit
Motor Purge Controller
Page 64 of 96
01-37A2-7D0003_Operating instructions_MPC_20210923_0_en.docx
Rev. 0
8
Commissioning
8.1
Initial commissioning
For systems that have been commissioned for the first time and have not yet
been parameterised, please follow the routine from Chapter 8.
If the Ex p control unit is in programming mode (parameter switch
activated and password entered), the pressure values are
displayed in Pa. Settings are made in the Pa.
General
The following procedure for setting the function parameters is recommended:
*
= Adjustment to be carried out in case of automatic purging
Start
Ex p Settings
Purging modes
Pressure
parameter
Characteristic
curve
*
Enclosure parameter
*
Options
Settings
Temperature sensors
Temp Sensor 1
Temp Sensor 2
Temp Sensor 3
Extended
Relay
Measuring units
Sensors
Network
Function test
Language
Safety device
Parameter
Ex p Parameter
Purging parameter