Ex p configuration
Ex p Control unit
APEX
mv
Page 60 of 80
01-37A2-7D0005_MV_Manual_Exp-Control-Unit_2021005_0_en.docx
Rev. 0
8
Ex p configuration
General
The following sections describe the initial commissioning of the Ex p control unit.
This means that it is described in detail how the Ex p control unit is set to the Ex
p equipment created.
COMMISSIONING
The operating instructions for the Ex p equipment must be
used for commissioning a set and certified Ex p equipment.
Sequence for the settings
The following procedure is recommended when setting the function parameters:
*
= Setting is to be performed in case of automatic flushing
Configuration
Make sure that the electrical wiring is as described in the
associated operating instructions and that the purge gas supply
is connected.
If the Ex p control unit is in programming mode (parameter switch
activated and password entered), the display of the pressure
values is in Pa. Settings are made in the Pa.
Log into the WEB interface in the User Level to perform the configuration.
Start
Ex p settings
Purge mode
Pressure parameter
Characteristics
*
Enclosure parameter
*
Options
Settings
Temp.-Sensors
Extended
Network
Functional test
Language
Settings backup
Parameter
Ex p parameters