7
Operation
The individual menus of the Ex p control unit are described in the following
chapters. Ex p specific configuration and settings are described in the
Commissioning chapter.
The complete solution is self-starting after connection of purging gas supply and
supply voltage. System states can be queried via the WEB interface.
WEB interface
The Ex p control station is supplied with a fixed IP address as standard.
Standard IP address (factory default): 192.168.11.101
The following options are available to establish a connection between laptop and
PC.
Laptop (192.168.11.99 // 255.255.0.0)
Direct
Indirect
USB / LAN interface converter
Ex p Control Unit (192.168.11.101)
Adjusting the LAN connection
Settings for the LAN interface on the PC (or converter / managed switch) must be
programmed so that it can communicate with the Ex p control unit.
Settings:
Configuration of the LAN interface:
Extended / speed: 100 Mbps full duplex
Properties of internet protocol Ver. 4 (TCP/IPv4):
Activation of fixed IP address
IP address: 192.168.11.99
Subnet mask: 255.255.0.0