B4: DIXELL OPERATING INSTRUCTIONS
dIXEL
Operating instructions
1592002701
1592002701 XH240L-V GB r1.0 12.01.2004 *
XH240L - XH240V
4/4
3.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Controller
memory, the “
doL
” message is blinking followed a by flashing
“End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the
“Hot Key”.
.
NOTE
the message “
Err
” is displayed for failed programming. In this case turn the unit off and
then on if you want to restart the download again or remove the “
Hot key
” to abort the operation.
11.
ALARM SIGNALLING
Message Cause
Outputs
“P1”
Thermostat probe failure
Compressor and heating outputs off
“P3”
Humidity probe failure
Humidity regulation off
“HA”
High temperature alarm
Outputs unchanged
“LA”
Low temperature alarm
Outputs unchanged
“HHA”
High humidity alarm
Outputs unchanged
“HLA”
Low humidity alarm
Outputs unchanged
“dA”
Door switch alarm
Outputs depending on the odC parameter
“EAL”
External alarm
Other outputs unchanged
“BAL”
Serious external alarm
Outputs OFF
“PAL”
Pressure switch alarm
Outputs OFF
The alarm message is displayed until the alarm condition recoveries.
All the alarm messages are showed alternating with the room temperature except for the “
P1
”
which is flashing. To reset the “EE” alarm and restart the normal functioning press any key, the
“
rSt
” message is displayed for about 3s.
11.1
SILENCING BUZZER
Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.
11.2
ALARM RECOVERY
Probe alarms
: “
P1
” (probe1 faulty), “
P3
” ; they automatically stop 10s after the probe restarts
normal operation. Check connections before replacing the probe.
Temperature alarms
“
HA
” and “
LA
” automatically stop as soon as the thermostat temperature
returns to normal values or when the defrost starts.
Humidity alarms
“
HHA
” and “
LHA
” automatically stop as soon as the humidity returns to
normal values.
Door switch alarm
“
dA
” stop as soon as the door is closed.
External alarms
“
EAL
”, “
BAL
” stop as soon as the external digital input is disabled
Pressure switch alarm
“
PAL” alarm is recovered by switching OFF the instrument
.
12.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case: XH240L:
facia 38x185 mm; depth 76mm
XH240V:
facia 100x64 mm; depth 76mm
Mounting: XH240L:
panel mounting in a 150x31 mm panel cut-out with two screws.
3 x 2mm.
Distance between the holes 165mm
XH240V:
panel mounting in a 56x72 mm panel cut-out with two screws.
3x2mm.
Distance between the holes 40mm
Protection:
IP20.
Frontal protection:
IP65 with optional frontal gasket mod. RG-L (XH240L); RGW-V (XH240V)..
Connections:
Screw terminal block
d
2,5 mm
2
heat-resistant wiring and 6,3mm Faston
Power supply:
230Vac or 110Vac
r
10%;
Power absorption:
7VA max.
Display
: double d icons.
Inputs
: 1 NTC probe + 4÷20mA probe
Digital input
: 1 free voltage
Relay outputs: compressor:
XH240L:
relay SPST 20(8) A, 250Vac;
XH240V:
relay SPST 8(3) A, 250Vac
heather:
relay SPST 8(3) A, 250Vac
fans:
relay SPST 8(3) A, 250Vac
humidifier:
relay SPST 8(3) A, 250Vac
Other output :
alarm buzzer (optional)
Data storing
: on the non-volatile memory (EEPROM).
Kind of action:
1B.;
Pollution grade:
normal;
Software class:
A.
Operating temperature:
0÷60 °C.;
Storage temperature:
-25÷60 °C.
Relative humidity:
20
y
85% (no condensing)
Measuring and regulation range:
NTC probe:
-40÷110°C (-58÷230°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
13.
WIRING CONNECTIONS
13.1
XH240L
R
oo
m
11
9 10
12 13
17
16
18 19
21
22 23
14 15
L
N
Comp
20(8)A
250V
~
6
2
7
3
8
4
5
1
Fan
8(3)A
250V
~
8(3)A
250V
~
8(3)A
250V
~
20
Heater
Hum
8(3)A
250V
~
Light
Supply 115Vac
: 14-15 terminals
13.2
XH240V
8(3)A250V
~
MAX
20A
Comp
Fan
R
o
om
Heater
8(
3)
A
8(
3)
A
8(
3)
A
C
Hum
8(
3)
A
Light
Supply 115Vac
: 2-3 terminals
14.
DEFAULT SETTING VALUES
Label Value Menu
Description
Range
Set T
5.0
- - -
Temperature Set Point
LS ÷ uS ( nu = temperature
regulation disabled )
Set H
50.0
- - -
Humidity Set Point
LSH ÷ uSH ( nu = humidity
regulation disabled)
dbt
2.0
Pr1
Half dead band width for temperature
0.1°C o 1°F ÷ 25°C o 77°F
dbH
5.0
Pr1
Half dead band width for humidity
0.5 ÷ 50
LS
-40
Pr2
Minimum temperature set point limit
-50.0°C o –58°F ÷ Set T
uS
110
Pr2
Maximum temperature set point limit
Set T ÷ 110°C o 230°F
odS
1
Pr2
Outputs activation delay at start up
0 ÷ 250 min
Ac
1
Pr1
Anti-short cycle delay
0 ÷ 30 min
LSH
0.0
Pr2
Minimum humidity set point limit
Lci ÷ Set H
uSH
100.0
Pr2
Maximum humidity set point limit
Set H ÷ uci
cF
°C
Pr2
Measurement unit
°C ÷°F
rES
dE
Pr2
Resolution (for °C):
in = integer / dE = decimal
rEH
Hd
Pr2
Resolution for RH%:
in = integer / Hd = half digit
idF
8
Pr1
Interval between defrosts
1 ÷ 120 h
MdF
20
Pr1
Duration of defrost
0 ÷ 250 min
dFd
it
Pr2
Display during defrost
rt / it / SEt / dEF / dEG
dAd
30
Pr2
Defrost display time out
0 ÷ 250 min
Hud
no
Pr2
Humidity control during defrost
no; yES
Fnc
c-n
Pr2
Fan operating mode
c-n / c-Y / o-n / o-Y
ALc
Ab
Pr2
Temperature alarm configuration
rE = relative / Ab = absolute
ALL
-40.0
Pr1
Low temperature alarm setting
0°C ÷ 50.0°C / -50.0°C ÷
ALu
ALu
110
Pr1
High temperature alarm setting
0°C ÷ 50.0°C / ALL ÷
110°C
ALH
1.0
Pr2
Temperature alarm recovery differential
0.1°C o 1°F ÷ 25°C o 77°F
ALd
15
Pr2
Temperature alarm delay
0 ÷ 250 min
dAo
1.3
Pr2
Delay of temperature alarm at start-up
0.0 ÷ 23.5 h
EdA
20
Pr2
Alarm delay at the end of defrost
0 ÷ 250 min
dot
20
Pr2
Delay of temperature alarm after closing
the door
0 ÷ 250 min
AHc
Ab
Pr2
Humidity alarm configuration
rE = relative / Ab = absolute
AHL
0.0
Pr1
Low humidity alarm setting
0 ÷ 50 / Lci ÷ AHu
AHu
100
Pr1
High humidity alarm setting
0 ÷ 50 / AHL ÷ uci
AHH
2.0
Pr2
Humidity alarm recovery differential
0.5 ÷ 25
AHd
15
Pr2
Humidity alarm delay
0 ÷ 250 min
dHo
1.3
Pr2
Delay of humidity alarm at start-up
0.0 ÷ 23.5 h
doH
20
Pr2
Alarm delay at the end of defrost
0 ÷ 250 min
nPS
0
Pr2
Pressure switch number
0÷15
doA
20
Pr2
Open door alarm delay
0 ÷ 250 min ( 250 = nu )
ot
0.0
Pr1
Thermostat probe calibration
-12.0 ÷ 12.0
o3
0.0
Pr1
Humidity probe calibration
-10 ÷ 10
P3P
yES
Pr2
Humidity probe presence
yES; no
Lci
0
Pr2
Readout with 4 mA
-999 ÷ 999
uci
100
Pr2
Readout with 20 mA
-999 ÷ 999
i1P
oP
Pr2
Digital input polarity
cL =open / oP = close
i1F
dor
Pr2
Digital input configuration
dor / PAL / EAL / bAL / Ht
odc
oFF
Pr2
Outputs status when open door
on / Fan / oFF
rrd
YES
Pr2
Outputs restarting after doA alarm
no = no / YES = yes
did
0
Pr2
Digital input alarm delay
0÷255 min.
Adr
1
Pr2
Serial address 1
0÷247
Ptb
1
Pr2
Parameter table
- - -
rEL
0.1
Pr2
Software release
- - -
Pr2
321
Pr1
Access to the protected parameter list
- - -
Dixell S.p.A. Via dell’Industria, 27
32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com
Содержание AGB
Страница 2: ...ii...
Страница 22: ...A1 WIRING DIAGRAM...