Barel reserves the right to change technical specifications without further notice
Page
6
of
7
TEST:
NOTE: A full test should not be activated when the battery is empty or low capacity - this could
result in a wrong error-message.
Manual test:
By disconnecting the mains when the battery has been charged for a minimum of 24 hours.
Status of the test must be observed manually. In case of failure: repair the problem and re-test or
reset unit by disconnecting mains.
Self-test:
By using a bipolar LED connected to the 2 of the 3 pins 5, 6 or 7 as shown above, then a self-test
will be performed. This test will automatically run a short test after 24h, then monthly and a full
annual test operating the LED module in emergency mode from the battery. The test-timer
includes a random-period to avoid all luminaires to self-test at the same time. Disconnection/reset
of mains and battery at the same time will reset the test-timer. Test-program is conducted acc to
IEC 62034.
Indicator
LED
(green) no
self-test
Indicator
LED
(red/green)
self-test
System
status
Action
Continuous
green
Continuous
green
System
ok
Battery charging ok and no faults apparent.
No light
Continuous
blinking
red
Battery
capacity
problem
24 h charge period after last discharge not completed, or faulty
battery. Retest system after 24h charging period, or replace
battery
No light
Intermittent
blinking
red
Faulty
LED
module
Replace faulty or missing LED module.
No light
Continuous
red
Charging
error
Battery defective or missing. Connect or replace battery.
No light
No light
No
function
Connect to mains supply voltage within specified limits.
4.5
Cable
Cable cross sectional area: 1 – 2,5 mm2 (solid or multi wire).
Terminal torque: 0,9Nm.
Terminal screw/tool: 0,6x3,5mm Slotted bit of high quality is recommended.
Suitable ferrule should be used to secure the connection of stranded wires.
For Aluminium cables; a bi metallic connector should be used to provide a copper connection.