TECHNICAL PRODUCT INFORMATION
Barel reserves the right to change technical specifications without further notice
5
Technical datasheet HFX and HFXE T8_10
4
Installation
These components does not cause harm or injury when used as specified in these instructions. If this equipment is not utilised in a manner specified by the
manufacturer, the protection by the equipment may be impaired.
4.1 Schedule of limitations:
The temperature of the TC point must not be exceeded
The minimum operating temperature of the ballasts is -30°C
Operating temperature of the plastic material used in the end cover is -30°C to +95°C
Operating temperature of the plastic material in the terminals is -30°C to +105°C
Charging current = 220mA, 80mA permanent
With one fault condition of the charging system, the charging power is limited to 2W by an transformer and the current is limited to 300mA
Discharge current = 0.9A - 1.75A
Discharge cut-off voltage = 4.0V for 4.8V battery and 7.2V for 8.4V battery
The fault current on the battery input is limited to 6.8A
Enhanced voltage according to Cl. 5.3.7.5. of IEC 60079-7, 304Vrms
The LED outputs has the following nominal ratings: 3V, 14mA and is limited to 5.4V and 18.3mA
The ballast shall be mounted inside an Ex e luminaire and not directly exposed to light
The terminal has a rating of 450V, Torque 0.5Nm and capacity on the screw side of one conductor with dimensions 1.0 - 2.5mm2 rigid or flex