The CMA-39 is a field-installable low ambient fan cycling 
control kit. This low ambient control is only for use on 
R-410A refrigerant systems. The low ambient control 
pressure sensor is attached to the suction line of the sys-
tem, and monitors low side system pressure. Operation 
of the LAC occurs as outdoor temperatures drop below 
the 65°F to 50°F range. On/Off LAC operation cycles the 
condenser fan operation based on outdoor temperature.
The CMA-39 kit is for use with Bard models W12AB, 
W30AB, W30LB, W36AB, W36LB, W42AC, W48AC, 
W60AC, W72AC, W3SAC, W4SAC and W5SAC wall-
mount air conditioners.
The CMA-39 kit consists of:
•  7960-848 Installation Instructions
•  8406-112 Low Ambient Fan Cycling Control
•  910-2058 Outdoor Temperature Switch Assembly
•  8408-048 Freeze Protect Thermostat
•  1012-066 3/4" Screw (1)
•  8607-017 Terminal Block
•  1012-085 1/2" Self-Tapping Screws (2)
•  7961-312-0482 CMA-39 Unit I.D. Label 

Field-supplied tools needed:

•  Personal protection equipment, including gloves 

and safety glasses

•  5/16" nut driver
•  1/2" wrench (service port) and 9/16" wrench (LAC 

control)

•  Phillips head screwdriver
•  Small flat head screwdriver for securing wire in 

terminal block

CMA-39 Low Ambient Fan Cycling Control

SUPPLEMENTAL INSTRUCTIONS

Sharp metallic edges.

Take care and wear appropriate protective 
devices to avoid accidental contact with 
sharp edges.

Failure to do so can result in personal 
injury.

!

CAUTION

Exposed moving parts.

Disconnect all electrical power before 
servicing.

Failure to do so can result in severe injury 
or amputation.

!

WARNING

Electrical shock hazard.

Disconnect the remote electric power 
supply or supplies before servicing.

Failure to do so can result in serious injury 
or death.

!

WARNING

Содержание CMA-39

Страница 1: ...Cycling Control 910 2058 Outdoor Temperature Switch Assembly 8408 048 Freeze Protect Thermostat 1012 066 3 4 Screw 1 8607 017 Terminal Block 1012 085 1 2 Self Tapping Screws 2 7961 312 0482 CMA 39 Un...

Страница 2: ...hat is tucked in the cable duct see Figures 1 or 2 Pull it out and connect it to the LAC terminal block on the terminal that is separate from the LAC control wire the purple wire in W12 units comes co...

Страница 3: ...ENT CONTROL TERM TO LOW AMBIENT AND REPLACE SEALING COMPOUND CONTACTOR BLUE WIRE TO BLACK OR TERMINAL BLOCK BROWN WIRE TO BLACK OR TERMINAL BLOCK BROWN WIRE TO BLACK OR BLACK OR ROUTE WIRES THROUGH BU...

Страница 4: ...Manual 7960 848B Page 4 of 12 FIGURE 2 W42AC W48AC W60AC W72AC W SAC MIS 4055 A PART 8607 017 COMPRESSOR PART 1012 066 SCREW COMPRESSOR CONTROL MODULE CONTACTOR TERMINAL BLOCK CABLE DUCT PHASE MONITOR...

Страница 5: ...REPLACE SEALING COMPOUND FROM FAN MOTOR BLACK WIRE BLACK WIRE TO CONTACTOR BLACK WIRE TO TERMINAL BLOCK ROUTE WIRES THROUGH BUSHING BLOCK CONTROL TERMINAL BLOCK TO LOW AMBIENT ATTATCH WIRE CONTACTOR T...

Страница 6: ...6 of 12 FIGURE 4 W30AB W30LB W36AB W36LB MIS 4056 SCREW PART 1012 085 RUN WIRES THROUGH THE BUSHING UP TO THE CONTROL PANEL LOW AMBIENT CONTROL PART 8406 112 1 2 WRENCH 9 16 WRENCH OUTDOOR TEMP SWITC...

Страница 7: ...ART 8406 112 MIS 4131 OUTDOOR TEMP SENSOR PLACEMENT 2 PLACES PART 910 2058 NUT SENSOR ASSEMBLY FOR EXTRA WIRE LENGTH OUTDOOR TEMP PART 1012 210 OUTDOOR TEMP SENSOR PART 7950 012 2 PLACES SCREW PART 10...

Страница 8: ...48B Page 8 of 12 FIGURE 6 W42AC W48AC W60AC W72AC W SAC MIS 4057 PART 8406 112 LOW AMBIENT CONTROL RUN WIRES UP BUSHING TO CONTROL PANEL OUTDOOR TEMP SWITCH ASS Y YELLOW WIRES PART 910 2058 2 SCREWS P...

Страница 9: ...W36 Freeze Stat Location and Wire Routing MIS 4054 USE ONE OF THE MIDDLE HEADER STUBS TO ATTACH THE FREEZE STAT TO THE EVAPORATOR COIL FREEZE STAT WIRES RUN DOWN COPPER THROUGH THE GROMMET AND INTO TH...

Страница 10: ...O ADDRESS EXTRA WIRE LENGTH TO EVAPORATOR COIL FREEZE STAT TO ATTACH FREEZE STAT USE BOTTOM DISTRIBUTOR TUBE FREEZE STAT NOTE USE PUSH MOUNT CABLE TIE PART 7950 012 ON THE BOTTOM SIDE OF THE BLOWER PA...

Страница 11: ...0 W72 W SAC Freeze Stat Location and Wire Routing USE ONE OF THE MIDDLE HEADER STUBS TO ATTACH THE FREEZE STAT TO THE EVAPORATOR COIL BLACK WIRES PART 8408 048 FEED WIRES THRU 1 SNAP BUSHING GOING INT...

Страница 12: ...mp Behind Low Voltage Block 12 Pin Plug Blue on UNITS 3 PHASE Low Ambient W24 Units MONITOR Outdoor Contactor Compressor Terminal Block 2 Control Module Compressor Brown on Black Black Yellow Yellow U...

Отзывы: