R5906150 /05
XDL
10
1.3 Important safety instructions
To prevent the risk of electrical shock
•
This product is equipped with a five-terminal barrier strip for the connection of a 3W+N+PE or 3W+PE
three phase power system.
•
This projector should be operated from an AC power source. Ensure that mains voltage and capacity
matches the projector electrical ratings.
•
Electrical ratings for Star system (3W+N+PE):
-
The cross-sectional area of the conductors in the power supply cord shall be 4 mm
2
to 6 mm
2
, 10 AWG
to 8 AWG.
-
The electrical rating of the XDL-4K60/75 projector is 200-240V/346-415V 3W+N+PE 16A 50-60Hz (Y
connection).
-
The electrical rating of the XDL-4K30 projector is 200-240V/346-415V 3W+N+PE 10A 50-60Hz (Y
connection).
-
The building installation has to be provided with a circuit breaker of 25-40 A to protect the complete
unit.
•
Electrical ratings for Delta system (3W+PE):
-
The cross-sectional area of the conductors in the power supply cord shall be 6mm
2
, 8AWG.
-
The electrical rating of the XDL-4K60/75 projector is 200-240V 3W+PE 28A 50-60Hz (Δ connection).
-
The electrical rating of the XDL-4K30 projector is 200-240V 3W+PE 15A 50-60Hz (Δ connection).
-
The building installation has to be provided with a circuit breaker of 40 A to protect the complete unit.
•
REMARK for XDL-4K60/75 projector:
In case of a Delta system (3W+PE) the circuit breakers rated lower
than 40A can trip unwanted because of the internal laser power supply redundancy system. The projector
remains working if one internal laser power supply module fails or is removed, but this results in a higher
current in one mains power line. In case of very low line voltage (between 180V and 200V), and one failed
or removed laser power supply, the line current can reach 35A.
•
Installation according to the local electrical code and regulations by qualified technical personnel only. Do
not defeat the purpose of the grounding.
•
The cross-sectional area of the UPS inlet cord shall be not less than 0.75 mm² or AWG 18.
•
The electronics of the projector (UPS INLET) must be powered either from a suitable UPS unit or from the
power outlet socket (UPS OUTLET) provided on the projector. An adapted short power cord (2-pole 3-wire
grounding) is added to the projector accessories to loop through the power from UPS OUTLET to UPS
INLET.
•
The provided power output socket (UPS OUTLET) on the projector may only be used to provide power to
the projector electronics (UPS INLET). Never connect other devices to this power output socket.
•
A readily accessible disconnect device must be incorporated externally to the equipment for removal of the
power to the projector mains terminals.
•
Disconnect the power to the projector mains terminals and unplug the power cord at UPS INLET for
removal of all power from the projector.
•
Warning: High leakage current. Earth connection essential before connecting supply.
•
Do not allow anything to rest on the power cord. Do not locate this projector where persons will walk on the
cord.
•
Do not operate the projector with a damaged cord or if the projector has been dropped or damaged - until it
has been examined and approved for operation by a qualified service technician.
•
Position the cord so that it will not be tripped over, pulled, or contact hot surfaces.
•
If an extension cord is necessary, a cord with a current rating at least equal to that of the projector should
be used. A cord rated for less amperage than the projector may overheat.
•
Never push objects of any kind into this projector through cabinet slots as they may touch dangerous
voltage points or short circuit parts that could result in a risk of fire or electrical shock.
•
Do not expose this projector to rain or moisture.
•
Do not immerse or expose this projector in water or other liquids.
•
Do not spill liquid of any kind on this projector.
•
Should any liquid or solid object fall into the cabinet, unplug the set and have it checked by qualified
service personnel before resuming operations.
•
Do not disassemble this projector, always take it to an trained service person when service or repair work
is required.
•
Do not use an accessory attachment which is not recommended by the manufacturer.
Содержание XDL
Страница 1: ...ENABLING BRIGHT OUTCOMES Installation Manual XDL...
Страница 30: ...R5906150 05 XDL 30 Installation process...
Страница 74: ...R5906150 05 XDL 74 Pulse SFP input use cases...
Страница 79: ...79 R5906150 05 XDL Dimensions A...
Страница 82: ...R5906150 05 XDL 82 Glossary...
Страница 86: ...R5906150 05 XDL 86 Index...
Страница 87: ......
Страница 88: ...www barco com R5906150 05 2021 08 02...