4. Physical installation

6. Power up the Custom Power Box.

Tip:

Measure the outgoing voltage on the power output connectors before connecting any devices with the power box.

7. Close and lock the Custom Power Box.

Image 4-3
Fixation nut on the backside of the Custom Power Box.

Image 4-4
Removed lower cover plate.

Image 4-5
Connector for power input.

4.3 Connections between custom power box and LED-wall

General

The custom power box is provided with multi-pole power output connectors. One multi-pole connector contains six (6) power circuits,
each protected with a 16 ampere rated circuit breaker.

A multi power cable is used to transport the power from the multi-pole connector to a spider connector. This spider connector
subdivide the power circuits into individual power source cables. Each power source cable of the spider connector leads to a group
of tiles. See installation manual of the involved tiles to know the maximum amount of tiles connected in parallel with the same power
source cable.

R5976620 CUSTOM POWER BOX 05/06/04

11

Содержание Custom power box

Страница 1: ...Custom power box Owners manual R5976620 02 05 06 04 ...

Страница 2: ...Barco nv Media Noordlaan 5 B 8520 Kuurne Phone 32 56 36 89 70 Fax 32 56 36 88 24 E mail media barco com Visit us at the web www barco com Printed in Belgium ...

Страница 3: ...ce or part of Barco If the purchaser or a third party carries out modifications or repairs on goods delivered by Barco or if the goods are handled incorrectly in particular if the systems are commissioned operated incorrectly or if after the transfer of risks the goods are subject to influences not agreed upon in the contract all guarantee claims of the purchaser will be rendered invalid Not inclu...

Страница 4: ......

Страница 5: ... Power Box 5 2 3 Technical summary 6 3 Cables used with the custom power box 7 3 1 Order info power cables 7 4 Physical installation 9 4 1 Components of a Custom Power Box 9 4 2 Installation 10 4 3 Connections between custom power box and LED wall 11 5 Addendum 13 5 1 Identification system of a power distribution network according IEC 364 13 Index 15 R5976620 CUSTOM POWER BOX 05 06 04 1 ...

Страница 6: ...Table of contents 2 R5976620 CUSTOM POWER BOX 05 06 04 ...

Страница 7: ...g to qualified service technicians personnel only Do not use this power box with an IT power distribution network A neutral conductor must be provided 1 2 Important Warnings Important warnings Risk of electrical shock Image 1 1 Risk of electric shock Do not open To reduce the risk of electric shock do not remove cover or back No user serviceable parts inside Refer servicing to qualified service pe...

Страница 8: ...1 Safety 4 R5976620 CUSTOM POWER BOX 05 06 04 ...

Страница 9: ... pole output connectors and 1 auxiliary outlet R9851241 Custom Power Box 3 phase 230VAC 3 multi pole output connectors and 1 auxiliary outlet R9851242 Custom Power Box 3 phase 230VAC 4 multi pole output connectors and 1 auxiliary outlet R9851243 Custom Power Box 3 phase 230VAC 5 multi pole output connectors and 1 auxiliary outlet R9851244 Custom Power Box 3 phase 230VAC 6 multi pole output connect...

Страница 10: ...Power boxes with four or more multi pole output connectors are provided with a ground fault current interrupter adjustable between 30 mA and 10 mA Multi pole output connectors 19 pins circular multi pole connectors with each 6 circuits Each circuit is protected with a 16 A switch fuse 20 kA short circuit rating Auxiliary connector 2 phase plus protective earth auxiliary connectors CEE form protect...

Страница 11: ...door use Used to distribute power between custom power box and spider connector image 3 1 image 3 2 R9851660 Waterproof spider connector for outdoor use with 6 power outputs C19 with different length Spider support bracket included Used to subdivide power from a multi power cable to a group of tiles image 3 3 image 3 6 R9851661 Waterproof spider connector for outdoor use with 6 power outputs C19 w...

Страница 12: ... connector plug Image 3 3 Waterproof spider connector output cables with different length Image 3 4 Waterproof spider connector output cables with same length Image 3 5 Spider connector for indoor use output cables with same length Image 3 6 Spider support bracket 8 R5976620 CUSTOM POWER BOX 05 06 04 ...

Страница 13: ... breaker is switched on Image 4 1 A Control lamp MAIN BREAKER ON B Auxiliary outlet C Multi pole power output connector D Multi pole power output connector E Multi pole power output connector F Multi pole power output connector G Door key Circuit breakers There are 6 circuit breakers provided per multi pole output connector The circuit breakers are marked with a letter which correspond to the lett...

Страница 14: ...ckside of the Custom Power Box is provided with a fixed M8 nut Use for every nut a M8 x 25 mm bolt for fastening the Custom Power Box image 4 3 2 Open the door of the Custom Power Box and place all the circuit breakers in the OFF position 3 Remove the lower cover plate inside the Custom Power Box by releasing four crosshead screws 4 Guide the incoming power cable through the cable seal at the bott...

Страница 15: ...tom power box is provided with multi pole power output connectors One multi pole connector contains six 6 power circuits each protected with a 16 ampere rated circuit breaker A multi power cable is used to transport the power from the multi pole connector to a spider connector This spider connector subdivide the power circuits into individual power source cables Each power source cable of the spid...

Страница 16: ...er connector will easily connect to the start point of a power branch 2 Fasten the multi pole plug of a spider connector inside the spider support bracket Warning Always use waterproof spider connectors in case of an outdoor LED wall application 3 Connect a single power source cable of the spider connector with the start point of a power branch of tiles in the LED wall 4 Repeat step 3 until all si...

Страница 17: ...an impedance The second character indicates the grounding manner of electrical equipment T Directly connected with the protective earth N Connected with the neutral conductor of the power source The third character indicates the situation of the neutral N conductor and the protective earth PE conductor C Common conductor for neutral and protective earth S Separated conductors for neutral and prote...

Страница 18: ...5 Addendum 14 R5976620 CUSTOM POWER BOX 05 06 04 ...

Страница 19: ...er box 11 Custom Power Box 5 6 Technical summary 6 F Functionality 5 I IEC 364 13 Installation 9 10 O Order info 5 7 P Power box 11 Connections 11 S Safety 3 Important Safety Instructions 3 Important Warnings 3 T Technical summary 6 R5976620 CUSTOM POWER BOX 05 06 04 15 ...