Banner SureCross Performance GatewayPro Series Скачать руководство пользователя страница 5

Modbus Holding Registers

I/O Point

Gateway

Node 1

Node 2

Node 3

Node 4

Node 5

Node 6

Node 7

15

15

31

47

63

79

95

111

127

16

16

32

48

64

80

96

112

128

EtherNet/IP

 Registers

EtherNet/IP on ControlLogix PLC Register Map
The DX80 wireless system is controlled by a ControlLogix PLC using EtherNet/IP through assembly objects and the Common Industrial
Protocol (CIP). Add the SureCross Gateway to the ControlLogix PLC as a “Generic Ethernet Module.”
There is one input assembly object for all DX80 input points and one output assembly object for all DX80 output points. Each object is
228 elements long, with each element a 16-bit integer.
The SureCross Gateway is configured at the factory to send all inputs and outputs for the first 16 Nodes in the system. To change the
factory settings, change the XML configuration file using the SureCross Web Configurator web pages.
Input Assembly Object, DX80 Input, Instance 100 (0x64). Words are not allocated for any specific unit but are used, in device order,
for each of the device input registers selected using the EIP checkbox.
Output Assembly Object, DX80 Outputs, Instance 112 (0x70). Words are not allocated for any specific unit but are used, in device
order, for each of the device output registers selected using the EIP checkbox.
For proper EtherNet/IP communication, the minimum requested packet interval should be 150 milliseconds or higher.

Instance 100

Instance 112

Word #

Inputs

Word #

Outputs

0

Input 1

0

Output 1

1

Input 2

1

Output 2

2

Input 3

2

Output 3

3

Input 4

3

Output 4

226

Input 227

226

Output 227

227

Input 228

227

Output 228

EtherNet/IP to PLC5 and SLC5 Register Map
Allen-Bradley’s PLC5 and SLC5 family of devices use PCCC communications over EtherNet/IP. The DX80 wireless system supports
these PLCs using input and output register arrays.
There is one input assembly object for all DX80 input points and one output assembly object for all DX80 output points. Each object is
228 elements long, with each element a 16-bit integer. The DX80 wireless data table addresses are N7 for read and N14 for write. The
MSG instruction only handles up to 103 words; use multiple MSG instructions if all data is required.

N7 - Read Registers

N14 - Write Registers

0

Input 1

0

Output 1

1

Input 2

1

Output 2

2

Input 3

2

Output 3

3

Input 4

3

Output 4

SureCross Performance GatewayPro

 

 

P/N 157639 Rev. B

www.bannerengineering.com - tel: 763-544-3164

5

Содержание SureCross Performance GatewayPro Series

Страница 1: ...to Banner Engineering s website www bannerengineering com surecross Models Power Frequency Feature DX80P9T6S P 10 to 30V dc 900 MHz ISM Band Modbus TCP or EtherNet IP communication protocol DX80P9A6S P Modbus TCP protocol Configuration capability using the Web Configu rator WARNING Not To Be Used for Personnel Protection Never use this product as a sensing device for personnel protection Doing so ...

Страница 2: ...e SureCross Performance GatewayPro combines in one unit the function of a SureCross Performance Gateway with the ability to interface to Ethernet using Modbus TCP or EtherNet IP protocols The GatewayPro has a serial port as well as an industrial Ethernet port There are two basic models of the GatewayPro DX80P T6 and DX80P A6 DX80P T6 The T6 model acts as a protocol converter only offering the Modb...

Страница 3: ... the black cover plate from the bottom of the device s cover The DIP switches are located behind the rotary dials After making the necessary changes to the DIP switches place the black cover plate back into position and gently push into place Plug the ribbon cable in after verifying that the blocked hole lines up with the missing pin Mount the cover back onto the housing DIP Switch Settings Switch...

Страница 4: ...r Node 1 are 17 through 32 as shown in the Modbus Holding Register table below Though only ten Nodes are shown the table can continue for as many Nodes as are used in a given network Using the equation or the Modbus Holding Registers table the register number for I O point 15 for Node 7 is 127 Modbus Holding Registers I O Point Gateway Node 1 Node 2 Node 3 Node 4 Node 5 Node 6 Node 7 1 1 17 33 49 ...

Страница 5: ... DX80 Outputs Instance 112 0x70 Words are not allocated for any specific unit but are used in device order for each of the device output registers selected using the EIP checkbox For proper EtherNet IP communication the minimum requested packet interval should be 150 milliseconds or higher Instance 100 Instance 112 Word Inputs Word Outputs 0 Input 1 0 Output 1 1 Input 2 1 Output 2 2 Input 3 2 Outp...

Страница 6: ...g the host s IP address open a web browser and log into the Ethernet Bridge GatewayPro or MultiHop Pro by typing the IP address in the browser location window http 192 168 0 1 After entering the IP address the home web page for the SureCross device displays To log in click on any tab at the top of the page To log out close the browser Admin level access allows administrators to set up system users...

Страница 7: ...on sulphur cured button covers Weight 0 26 kg 0 57 lbs Mounting 10 or M5 SS M5 hardware included Max Tightening Torque 0 56 N m 5 in lbf Antenna Connection Ext Reverse Polarity SMA 50 Ohms Max Tightening Torque 0 45 N m 4 in lbf Interface Indicators Two bi color LEDs Buttons Two Display Six character LCD Wiring Access One 5 pin Euro style male connector and One 4 pin fe male industrial Ethernet co...

Страница 8: ...t any time For the most recent version of any documentation refer to our website www bannerengineering com 2006 2010 Banner Engineering Corp All rights reserved Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one year following the date of shipment Banner Engineering Corp will repair or replace free of c...

Отзывы: