Wire No.
Wire Color
Description
1
2
3
4
5
1
Brown
10 to 30V dc
2
White
RS485 / D1 / B / +
3
Blue
dc common (GND)
4
Black
RS485 / D0 / A / –
5
Gray
Comms Gnd
Industrial Ethernet Wiring
Use the 4-pin industrial Ethernet connection to connect the radio network to an Ethernet-based host system.
Wire No.
Wire Color
Description
1
White/Orange
+Tx
2
White/Blue
+Rx
3
Orange
-Tx
4
Blue
-Rx
Modbus Holding Registers
There are sixteen Modbus holding registers for each SureCross
™
device. Calculate the holding register number for each device using
the equation: Register number = I/O# + (Node# × 16).
Because the Gateway is always device 0, the Gateway’s holding registers are registers 1 through 16. Registers for Node 1 are 17
through 32, as shown in the Modbus Holding Register table below. Though only ten Nodes are shown, the table can continue for as many
Nodes as are used in a given network.
Using the equation or the Modbus Holding Registers table, the register number for I/O point 15 for Node 7 is 127.
Modbus Holding Registers
I/O Point
Gateway
Node 1
Node 2
Node 3
Node 4
Node 5
Node 6
Node 7
1
1
17
33
49
65
81
97
113
2
2
18
34
50
66
82
98
114
3
3
19
35
51
67
83
99
115
4
4
20
36
52
68
84
100
116
5
5
21
37
53
69
85
101
117
6
6
22
38
54
70
86
102
118
7
7
23
39
55
71
87
103
119
8
8
24
40
56
72
88
104
120
9
9
25
41
57
73
89
105
121
10
10
26
42
58
74
90
106
122
11
11
27
43
59
75
91
107
123
12
12
28
44
60
76
92
108
124
13
13
29
45
61
77
93
109
125
14
14
30
46
62
78
94
110
126
SureCross Performance GatewayPro
4
www.bannerengineering.com - tel: 763-544-3164
P/N 157639 Rev. B