Battery Life Calculations
Analog Configuration
The battery life calculations, in years, for some analog sensors are shown in the table below.
Table 1: Battery Life in Years
Manufacturer
Device
Model
Boost Voltage
Warmup Time
1
Banner
U-Sonic/Distance
QT50ULBQ6-75390
15V
500 ms
2
Esterlink/KPSI
Submersible Level
KPSI Series 700
10V
10 ms
3
Turck
Pressure
PT100R-11-L13-H1131
10V
10 ms
Sample and Report Rates
1 second
2 seconds
4 seconds
16 seconds
64 seconds
5 minutes
15 minutes
1
0.00
0.00
0.00
0.26
0.91
2.61
4.45
2
0.87
1.45
2.15
3.32
3.89
4.25
4.25
3
0.87
1.45
2.15
3.32
3.89
4.25
4.25
Note, battery life calculations are based on the sensor operating 24 hours a day, 365 days a year.
QT50ULBQ6-75390
PT100R-11-L13-H1131
KPSI Series 700
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
1 sec
2 sec
4 sec
16 sec
64 sec
5 min
15 min
Sample and Report Rates
D
X81
B
att
er
y
Li
fe
(Y
ea
rs
)
For each sensor characterized, a boost voltage and warmup time was specified. The sample and reports rates were varied to calculate
the estimated battery life. For example, a Banner QT50ULBQ6-75390 sensor set to a boost voltage of 15 volts, a warm-up time of 500
milliseconds, and a sample and report rate of 15 minutes, should have a battery life of 4.45 years.
All battery life calculations are approximations based on a strong radio signal. Weaker radio connections and missed packets will de-
crease the battery life.
SureCross Wireless I/O Network Manual
rev. I
www.bannerengineering.com - tel: 763-544-3164
75