
Disable Ethernet Port
Set to on to power down the Ethernet interface. Disabling the unused Ethernet port reduces power consumption.
The factory default position is OFF.
Disable LCD Display
Set to on to disable the LCD. This DIP switch should be on when the LCD display board is not connected.
The factory default position is OFF.
4.4 Ethernet
Before applying power to the DXM, verify the Ethernet cable is connected.
The number of times the processor attempts to connect to the Ethernet network is configured in the DXM Configuration
Software (
Settings
>
Network Ethernet Connection Acquisition
). The default setting is two retries one minute after the
device boots up another retry two minutes later.
The Ethernet connection supports the DXM Configuration Software, Modbus/TCP, and EtherNet/IP. ScriptBasic also has
access to Ethernet for custom programming. Use the software or LCD menu system to configure the characteristics of the
Ethernet connection, including the IP address. Any parameters not changeable from the menu system are configurable from
the configuration software.
Ethernet parameter changes entered through the LCD menu override the XML configuration parameters. To return to using
the network settings in the XML configuration file, remove the Ethernet parameters defined by the LCD menu using the
System Config
>
Ethernet
>
Reset
menu.
4.5 USB
The USB port is used with the DXM Configuration Software to program the DXM100/1000-Bx Wireless Controller. The USB
port is also used as the console output for the processor and ScriptBasic.
Turn on debug messages to the serial console by selecting
Print push debug messages to serial console
in the DXM
Configuration Software
Settings
>
Cloud Services
screen.
Sure Cross
®
DXM100-Bx and DXM1000-Bx Wireless Controllers
www.bannerengineering.com - Tel: + 1 888 373 6767
23