Programmable Safety Controller SCR P
www.bernstein.eu
- Tel: + 49 571 793 0
93
Network Settings
Network Settings: Modbus/TCP, Ethernet/IP, PCCC
Click
Network Settings
on the Software to open the
Network Settings
window. In the case of a Modbus/TCP connection,
the default TCP port used is 502, by specification. This value is not shown in the
Network Settings
window.
Table 7: Default Network Settings
Setting Name
Factory Default Value
IP Address
192.168.0.128
Subnet Mask
255.255.255.0
Gateway Address
0.0.0.0
Link Speed and Duplex Mode
Auto Negotiate
An
Actuation Code
is required for configurations containing a virtual manual reset or cancel delay input.
The
Advanced
option allows further configuration of Modbus/TCP and EtherNet/IP settings, such as Swap character bytes,
MSW and LSW sending precedence, and String Length Type (EtherNet/IP and PCCC).
Click
Send
to write the network settings to the Safety Controller. Network settings are sent separately from the
configuration settings.
Click
Network Timeout Enabled
to have any configured Virtual On/Off or Virtual Mute Enable become inactive in the event of
a network timeout condition. The network timeout time is fixed at 5 seconds.
Note:
Use
Password Manager
to enable or disable the ability for User2 and User3 to change the network
settings.
Figure 77: Network Settings