System Lockout
Indicates a Non-Operating Lockout Condition, for example unmapped input connected to 24 V.
7.10 Virtual Status Outputs
Up to 64 Virtual Status Outputs can be added for any configuration using Modbus/TCP, EtherNet/IP Input Assemblies,
EtherNet/IP Explicit Messages, and PCCC protocols on FID 1 Base Controllers and up to 256 virtual Status Outputs can be
added on FID 2 Base Controllers and SC10-2 Safety Controllers. FID 2 Base Controllers and SC10-2 Safety Controllers can
also use PROFINET. These outputs can communicate the same information as the Status Outputs over the network. See
on page 60 for more information. The Auto Configure function, located on the Industrial
Ethernet tab of the Software, automatically configures the Virtual Status Outputs to a set of commonly used functions,
based on the current configuration. This function is best used after the configuration has been determined. Virtual Status
Output configuration can be manually revised after the Auto Configure function has been used. The information available
over the network is consistent with the logical state of the inputs and outputs within 100 ms for the Virtual Status Output
tables (viewable via the Software) and within 1 second for the other tables. The logical state of inputs and outputs is
determined after all internal debounce and testing is complete. See
on page 102 for details on
configuring Virtual Status Outputs.