Cancel Off-Delay Timing
Off Delay
Time Limit
1
Note 1 - If “turn output off” function is selected
Safety Inputs
Cancel Delay Input
SO1 or
Delay Block Output
Figure 18. Safety Input remains in Stop mode
0.5 sec.
Safety Inputs
Cancel Delay Input
SO1 or
Delay Block Output
Off Delay
Time Limit
Figure 19. Turn Output Off function
Safety Inputs
Latch Reset Input
Cancel Delay Input
SO1
On
Off
Off Delay
Time Limit
Figure 20. Keep Output On function for Safety Inputs with the Latch Reset
Off Delay
Started
Off Delay
Ended
Off Delay
Normal End
Cancel Delay
Performed
Safety Inputs
Cancel Delay Input
SO1 or
Delay Block Output
Off Delay
On
Off
Figure 21. Keep Output On function for Safety Inputs without the Latch
Reset
7.6.1 Manual Reset Input
The Manual Reset input may be configured to perform any combination of the following (see
on page 62):
Reset of Safety Inputs
Sets the output of the Latch Reset Block(s) to a Run state from a Latched state when the IN node is in a Run state
Reset of Safety Outputs
Sets the Output to On if the Output Block configured for Latch Reset is On.
Exceptions:
A Safety Output cannot be configured to use a Manual Reset when associated with a Two Hand Control input or an
Enabling Device Function Block.
System Reset
Sets the System to a Run state from a Lockout state due to a system fault. Possible scenarios when System Reset
is needed include:
• Signals are detected on unused terminal pins
• Configuration Mode timeout
• Exiting Configuration Mode
• Internal faults
Output Fault Reset
Clears the fault and allows the output to turn back On if the cause of the fault has been removed. Possible
scenarios when an Output Fault Reset is needed include:
• Output faults
• EDM or AVM faults
XS/SC26-2 and SC10-2 Safety Controllers
42