Software Code Error
J.1
A Two-Hand Control Block can be connected only to an Enabling Device Block (IN node) or a Safety Output (IN node).
J.3
Only Two-Hand Control inputs or Bypass Blocks with Two-Hand Control inputs connected to them can be connected to the TC node
of a Two-Hand Control Block.
K.1
A Two-Hand Control input can be connected only to a Two-Hand Control Block (TC node) or Bypass Block (IN node).
K.2
A Safety Output that has
Safety Output Delay
set to "Off Delay" cannot be connected to a Two-Hand Control Block.
K.3
A Safety Output that has
Safety Output Delay
set to "Off Delay" cannot be connected to a Two-Hand Control Block via an Enabling
Device Block.
L.1
This Safety Output is disabled because a Status Output is using its terminals.
L.2
The IN node of a Safety Output cannot be connected to External Device Monitoring, Adjustable Valve Monitor, Mute Sensor Pair,
Bypass Switch, Manual Reset, Mute Enable, or Cancel Off Delay inputs.
L.3
A Safety Output block that has
LR (Latch Reset)
function enabled cannot be connected to Two-Hand Control Blocks or Enabling
Device Blocks.
L.4
A Safety Output block that has
Power up Mode
set to "Manual Reset" cannot be connected to Two-Hand Control Blocks or Enabling
Device Blocks.
13.3 Verifying Driver Installation
This section applies to both the XS/SC26-2 and the SC10-2.
Windows 7, 8 and 10
1. Click Start.
2. Type "Device Manager" in the
Search for programs and files
field at the bottom and click Device Manager when
Windows locates it.
3. Expand the Ports (COM & LPT) dropdown menu.
4. Find XS26-2 Expandable Safety Controller followed by a COM port number (for example, COM3). It must not have
an exclamation mark, a red ×, or a down arrow on the entry. If you do not have any of these indicators, your device
is properly installed. If any of the indicators appear, follow the instructions after this table to resolve these issues.
XS/SC26-2 Safety Controller Drivers
1. Expand the Ports (COM & LPT) dropdown menu.
2. Find XS26-2 Expandable Safety Controller
followed by a COM port number (for example,
COM3). It must not have an exclamation mark, a
red ×, or a down arrow on the entry. If you do not
have any of these indicators, your device is
properly installed. If any of the indicators appear,
follow the instructions after this table to resolve
these issues.
SC-XMP2 Drivers
1. Expand the Universal Serial Bus controllers
dropdown menu.
2. Find XMP2 Programmer A and XMP2 Programmer
B. Either one of the entries must not have an
exclamation mark, a red ×, or a down arrow on the
entry. If you do not have any of these indicators,
your device is properly installed. If any of the
indicators appear, follow the instructions after this
table to resolve these issues.
XS/SC26-2 and SC10-2 Safety Controllers
146