9.8.1 Network Settings
Network Settings: Modbus/TCP, Ethernet/IP, PCCC
Figure 88. Network Settings
Click
Network Settings on the Software to open the Network Settings window. In the case of a Modbus/TCP connection,
the default TCP port used is 502, by specification. This value is not shown in the Network Settings window.
Table 5: Default Network Settings
Setting Name
Factory Default Value
IP Address
192.168.0.128
Subnet Mask
255.255.255.0
Gateway Address
0.0.0.0
Link Speed and Duplex Mode
Auto Negotiate
The Advanced option allows further configuration of Modbus/TCP and EtherNet/IP settings, such as Swap character bytes,
MSW and LSW sending precedence, and String Length Type (EtherNet/IP and PCCC).
Click Send to write the network settings to the Safety Controller. Network settings are sent separately from the
configuration settings.
Click Network Timeout Enabled to have any configured Virtual On/Off or Virtual Mute Enable become inactive in the event of
a network timeout condition. The network timeout time is fixed at 5 seconds.
Note: Use Password Manager to enable or disable the ability for User2 and User3 to change the network
settings.
XS/SC26-2 and SC10-2 Safety Controllers
www.bannerengineering.com - Tel: + 1 888 373 6767
103