14.3.1 General Command Execution
Point of View of the PLC
Start
(Optional)
If using Command
ID, set it and its
Parameter value
as required
Done
Read Error Code.
Handle error
condition.
Clear all
Output Flags
Is Execution
Error flag set?
Command execution
successful. Read value
and input status flags as
required
ACK Flag set?
Set Command
Output Flag
Yes
No
Yes
No
The following rules apply for the use of input bit commands:
• Only one iVu BCR input bit can be set at a time
• Corresponding ACK bits are set high only on completion of
the command (if the iVu BCR input bit is still high)
• Corresponding ACK bits are cleared when the iVu BCR
input bit is cleared
• When multiple iVu BCR input bits are set simultaneously,
the Execution Error input bit is set and an Error Code value
is reported in the Error Code register
• The Execution Error iVu BCR output bit is cleared when all
ACK bits are cleared, or a new valid command is received
14.4 EtherNet/IP
™
In this context, references to EtherNet/IP refer specifically to EtherNet/IP
™
10
transport class 1. Sometimes referred to as
cyclic EtherNet/IP IO data transfer or implicit messaging, this connection is meant to approximate a real-time data transfer
to and from the PLC and the target device.
10
EtherNet/IP
™
is a trademark of ODVA, Inc.