Overcurrent protection is required to be provided by end prod-
uct application per the supplied table.
Overcurrent protection may be provided with external fusing
or via Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go
to
www.bannerengineering.com
.
Supply
Wiring
(AWG)
Required Overcurrent
Protection (A)
Supply
Wiring
(AWG)
Required Overcurrent
Protection (A)
20
5.0
26
1.0
22
3.0
28
0.8
24
1.0
30
0.5
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Op-
eration of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Industry Canada Statement for Intentional Radiators
This device contains licence-exempt transmitters(s)/receiver(s) that comply with Innovation, Science and Economic Develop-
ment Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
Cet appareil contient des émetteurs/récepteurs exemptés de licence conformes à la norme Innovation, Sciences, et
Développement économique Canada. L’exploitation est autorisée aux deux conditions suivantes:
File System and Archive Process
The DXM file system is in a serial EEPROM that stores non-volatile configuration information. The serial EEPROM stores ba-
sic data that is required to be non-volatile, including network configuration data, IP address, MAC address, network masks,
firewall settings, and authentication information.
The controller XML configuration file created by the
DXM Configuration Software
is stored in EEPROM. The small section of
non-volatile local registers is also stored in EEPROM.
Update Your DXM Processor Firmware Using the Configura-
tion Software
To update your processor firmware using the
DXM Configuration Software
, follow these instructions.
This device may not cause interference.
1.
This device must accept any interference, including interference that may cause undesired operation of the device.
2.
L’appareil ne doit pas produire de brouillage.
1.
L’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en
compromettre le fonctionnement.
2.
Using the
DXM Configuration Software
version 4 or later, connect to the
DXMR90-X1
via Ethernet.
File loads to the
DXMR90-X1
will take several minutes.
1.
On the
DXM Configuration Software
, go to
Tools
›
Reprogram
›
Get Device Information
to verify the current firmware
version.
You must load a different version with the same firmware number for the bootloader to operate. Download firmware
files from the Banner website.
2.
© Banner Engineering Corp.
Содержание DXMR90-X1 Series
Страница 4: ...Blank page 4...
Страница 10: ...Blank page 10...
Страница 18: ...Blank page 18...
Страница 24: ...May 09 2023 DXMR90 X1 Series Controller Instruction Manual 24 Slave Port 0 Settings Banner Engineering Corp...
Страница 48: ...Blank page 48...
Страница 55: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...