Configuring the Controller
Use the configuration software to define the
Protocol conversion
for each local register to be
EIP Originator
›
DXM
or
EIP
DXM
›
Originator
from the
Edit Register
or
Modify Multiple Register
screens.
Define a DXM local register as
EIP Originator
›
DXM
when the host PLC (Originator) will send data to the
DXMR90-X1
local
register (DXM).
Define a DXM local register as
EIP DXM
›
Originator
when that register data will be sent from the
DXMR90-X1
(DXM) to the
host PLC (Originator).
Data from an EIP controller in assembly instance 112 is data destined for the
DXMR90-X1
local registers. The PLC is normal-
ly configured for INT or UINT data transfer. This allows for a seamless transfer of data.
EIP Assembly Instance 112 (16-bit)
DXM Local Registers
Adrs
Data
Adrs
Data
0
1122
1
1122
1
3344
2
3344
2
5566
3
5566
3
7788
4
7788
4
9900
5
9900
Data from the
DXMR90-X1
local registers is sent to the EIP controller using assembly instance 100. Each local register in
the
DXMR90-X1
defined as
EIP DXM
›
Originator
is collected in numerical order and placed into the data buffer destined for
assembly instance 100. DXM local registers are capable of 32-bits, but only the lower 2-bytes (16-bits) for each local register
are transferred.
EIP Assembly Instance 100 (16-bit)
DXM Local Registers
Adrs
Data
Adrs
Data
0
1122
11
1122
1
3344
12
3344
2
5566
13
5566
3
7788
14
7788
4
9900
15
9900
Set up the Email
The
DXMR90-X1
can be configured to send email messages based on threshold conditions.
Ethernet-connected systems can only use email, but can send email to cellular phones as a SMS message depending upon
the network carrier. To send email to a Verizon phone, use the phone number followed by
@vtext.com
, for exam-
ple,
.
For more information, refer to the DXM Configuration Software Instruction Manual (p/n
). Follow these instructions
and use the
DXM Configuration Software
to program the controller for email.
On the
Settings
›
System
screen, set the
Device Time
on the
DXMR90-X1
.
1.
On the
Settings
›
Cloud Services
screen, select Ethernet for the
Push Interface
.
2.
Configure your Ethernet connection by setting the IP settings on the
Ethernet
screen.
3.
Set the email and message parameters on the
Notifications
screen.
4.
To send alert messages, define the threshold rule to use email.
5.
© Banner Engineering Corp.
Содержание DXMR90-X1 Series
Страница 4: ...Blank page 4...
Страница 10: ...Blank page 10...
Страница 18: ...Blank page 18...
Страница 24: ...May 09 2023 DXMR90 X1 Series Controller Instruction Manual 24 Slave Port 0 Settings Banner Engineering Corp...
Страница 48: ...Blank page 48...
Страница 55: ...LinkedIn Twitter Facebook 2023 All rights reserved www bannerengineering com...