DXM700-Bx Wireless Controller Instruction Manual

March 29, 2023

© 

Banner Engineering Corp. All rights reserved.

Содержание DXM700-B1R1

Страница 1: ...DXM700 Bx Wireless Controller Instruction Manual March 29 2023 Banner Engineering Corp All rights reserved...

Страница 2: ...ches 14 Application Mode 15 Baud Rate and Parity 15 Disable Serial 15 Transmit Power Levels Frame Size 15 Modbus Registers for the MultiHop Radio Board Module 16 DIP Switch Settings for the Performanc...

Страница 3: ...Slots and Retry Count Parameters 41 Calculating the Communication Timeout for a DX80 Star Network 41 Modbus TCP Client 42 Chapter 8 Configuration Instructions 43 Scheduler 43 Create a Weekly Event 43...

Страница 4: ...ls 59 DXM700 Documentation 59 DXM Support Policy 59 Firmware Updates 60 Website Information 60 Feature Requests 60 Potential DXM Issues 60 DXM Security 60 Contact Us 60 Certifications and Standards 60...

Страница 5: ...ocal registers Modbus ID 199 Local Registers Type Description 1 845 32 bit integer Local data registers 846 849 32 bit integer Reset Constant Timer 851 900 32 bit non volatile integer Data flash non v...

Страница 6: ...units on a grounded static dissipative surface The top housing contains the LCD display board The display board is connected to the base board using a ribbon cable with a 20 pin connector Figure 1 DXM...

Страница 7: ...ure the port parameters using the configuration software Modbus TCP IP A host system acting as a Modbus client can access the DXM using the Modbus TCP IP protocol over Ethernet Standard Modbus port 50...

Страница 8: ...nal Modbus IDs factory default Modbus ID Device 1 DX80 Performance Gateway or MultiHop ISM Radio MultiHop wireless devices connected to the internal MultiHop radio should be assigned Modbus addresses...

Страница 9: ...ile governs all aspects of the DXM operation The wireless network devices are a separate configurable system Use the DX80 User Configuration Software to configure the internal DX80 wireless Gateway an...

Страница 10: ...XM700 BX 1 5 Dimensions All measurements are listed in millimeters inches unless noted otherwise 60 mm 2 36 35 5 mm 1 4 70 mm 2 76 86 mm 3 39 94 5 mm 3 72 58 1 mm 2 29 28 8 mm 1 13 52 8 mm 2 08 ISM ra...

Страница 11: ...adios to the internal ISM radio If you are having difficulty running binding or site surveys it may be because of the speed of the XML configuration file or script running on the DXM To resolve this i...

Страница 12: ...hin the same network The MultiHop client radio automatically generates a unique binding code when it enters binding mode This code is transmitted to all radios within range that are also in binding mo...

Страница 13: ...assistance 2 1 3 Set a Static IP Address Change the IP address of the DXM to connect to a local area network Modbus TCP IP host controller or EtherNet IP host controller CONTEXT There are two ways to...

Страница 14: ...ns are available for all models To change to another model of DXM go to the Connect to DXM screen and use the drop down list to select another model If the active configuration is incompatible with th...

Страница 15: ...six registers on an external Modbus server device and save the data into the local regis ters The software only loads a file to the DXM Internal parameter settings that are changed in the tool but not...

Страница 16: ...error condition For this example if the read function fails after three attempts the read rule writes 12345 to the DXM local registers Notice the list of local register names this read rule is using S...

Страница 17: ...over damage or liability for misuse abuse or the improper application or installation of the Banner product THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IM...

Страница 18: ...power Flashing green MultiHop ISM radio LED indicates operation Red and green combined Communications traffic and binding 3 1 MultiHop Radio DIP Switches MultiHop ISM radio devices are defined with R2...

Страница 19: ...1 3 Disable Serial Disable an unused local serial connection to reduce the power consumption of a data radio powered from the solar assembly or from batteries All radio communications remain operation...

Страница 20: ...itch is disabled The transmit power for 2 4 GHz is fixed at about 65 mW EIRP 18 dBm DX80 Performance Gateway ISM radio devices are defined with R1 R3 and R8 in the model number DXMxxx xxR1 DX80 Perfor...

Страница 21: ...The register groups include the input output registers bit packed registers and analog registers This feature is only available with the Performance models using version 3 or newer of the LCD firmwar...

Страница 22: ...424 Node 2 Outputs 1 through 8 2577 2584 Node 47 Inputs 1 through 8 4777 4784 Node 47 Outputs 1 through 8 Table 8 Discrete bit packed registers for inputs and outputs Sheet 1 of 2 Inputs Outputs Modbu...

Страница 23: ...y I O point using Modbus registers 6801 through 9098 For example Input 1 for Gateway and all Nodes is stored in the first 48 contiguous blocks of 16 bit analog registers beginning with register 6801 I...

Страница 24: ...move a cellular modem when the power to the device is disconnected Force Cloud Push Button Press and hold this button for five seconds to send an immediate push message from the device if properly con...

Страница 25: ...not changeable from the menu system are configurable from the configuration software Ethernet parameter changes entered through the LCD menu override the XML configuration parameters To return to usin...

Страница 26: ...ters that show the internal variables of the main processor Some register values will be dependent upon the configuration settings of the DXM700 Do not use Read Rules to move virtual local registers d...

Страница 27: ...rrors 10108 Write map success streak 10109 Number of passthrough successes API message passing statistics 10110 Number of passthrough timeouts 10111 Number of passthrough errors 10112 Passthrough succ...

Страница 28: ...ISM radio the local I O base board and the local display board As a Modbus RTU server device the DXM local registers can be read from or written to by another Modbus RTU client device The secondary p...

Страница 29: ...client and server Settings include None default odd even space and mark Timeout Applies to the Modbus client port Covers the expected time for messages to be sent throughout the wireless network For t...

Страница 30: ...for the bus with the board and the processor board are fixed External Modbus communication runs at a maximum rate of 50 ms per transaction The parameter settings for the external RS 485 buses are cont...

Страница 31: ...ocument to activate the cellular capabilities of your DXM Controller 1 Purchase a cellular modem kit from Banner Engineering Corp 2 Install the cellular modem connect the antenna cable and connect the...

Страница 32: ...and SIM card that will only allow the SIM to be inserted with one orientation Do not force the SIM card into the socket SXI CATM1ATT 001 AT T CAT M1 cellular modem using Telit ME910 modem kit AT T par...

Страница 33: ...ered by warranty Use proper handling procedures to prevent ESD damage Proper handling procedures include leaving de vices in their anti static packaging until ready for use wearing anti static wrist s...

Страница 34: ...nna connection 5 3 1 3 Activate a 4G LTE CAT M1 Cellular Plan Activate a cellular plan for your DXM700 using the Banner Cloud Data Services website 1 Go to secure bannercelldata com to purchase cellul...

Страница 35: ...l support person to identify and purchase machine to machine M2M data plan only SIM cards in 3FF micro form factor Typical monthly data use will be 20 50 MB per month When choosing a plan pay close at...

Страница 36: ...ces screen Set the Cloud push interval and the Web Server settings For more information refer to the DXM Configuration Software Instruction Manual p n 201127 Figure 8 The Settings Cloud Services scree...

Страница 37: ...censed to resell Verizon network data plans The SXI LTE 001 or SXI CATM1VZW 001 will not function on AT T T Mobile or Sprint networks When purchasing a data plan it is important to refer to the modem...

Страница 38: ...uration Software Figure 2 Registers menu To configure these local registers launch the DXM Configuration Software Go to Local Registers and expand the view for a local register by clicking on the down...

Страница 39: ...ucting a Site Survey with the ISM Radio on page 7 For more information on binding a particular device refer to the individual datasheet Site Survey After creating a wireless network using the binding...

Страница 40: ...dio If set incorrectly the DXM700 may not be able to run Site Survey from the LCD menu Unless you are changing or adding the internal radio device there should no reason to change the radio type Refer...

Страница 41: ...nt Identifier MDN Mobil Device Number version signal firewall setting and firewall mask Some of these parameters are not visible until the cellular network is accessed Wifi Displays the Wifi IP addres...

Страница 42: ...color LEDs using the display board s Modbus registers Using write maps or ScriptBasic write the Modbus registers shown below with 0 off or 1 on The LCD display is Modbus ID 201 Table 1 Modbus Registe...

Страница 43: ...oftware The DXM700 operates the Modbus client port Each device on the client port must be assigned a unique device ID There are device IDs that are reserved for internal devices in the DXM700 7 1 Assi...

Страница 44: ...n a MultiHop network must be assigned a unique Modbus ID and is accessed as a separate device For the DXM to talk with a MultiHop device in the wireless network the client MultiHop device interrogates...

Страница 45: ...are running at the highest communications rate the overall effect is not as great Client to Repeater Send time 9 0 04 sec 8 retry wait 0 04 sec 1 second Repeater to Client Send time 9 0 04 sec 8 retr...

Страница 46: ...t The DXM700 can operate as a Modbus TCP client on Ethernet Users may define up to five socket connections for Modbus TCP server devices to read Modbus register data over Ethernet Use the DXM Configur...

Страница 47: ...xpand the parameters into view STEP RESULT The user defined parameters are displayed 3 Name your new rule 4 Enter the local register 5 Select the days of the week this rule applies to 6 Enter the star...

Страница 48: ...re 3 Scheduler Holidays screen 1 Click on Add Holiday STEP RESULT A new rule is created 2 Enter a name your new holiday rule 3 Select the start date and time for the new holiday 4 Select the stop date...

Страница 49: ...M700 can be programmed to allow changes to the configuration files only with proper authentication by setting up a password on the Settings Administration screen in the DXM Configuration Software With...

Страница 50: ...n View Local Registers using the Local Registers Local Registers in Use screen of the DXM Configuration Software When a configuration is running on the DXM700 viewing the Local Registers can help you...

Страница 51: ...eneric device with the product name of Banner DXM ProdType 43 Generic Device ProdName Banner DXM Integer Type INT IMPORTANT Do not set the Requested Packet Interval RPI any faster than 150 ms 8 4 2 Co...

Страница 52: ...et go to the Settings Ethernet screen 1 To define the Ethernet IP address give the DXM700 a static IP address In most cases you may select the device to use DHCP and have the IP address automatically...

Страница 53: ...ive retry attempts immediately follow each other After all attempts are exhausted the register data packet is saved on the micro SD card At the next scheduled time the DXM700 attempts to send the save...

Страница 54: ...across a variety of tools as a standard set of device information 9 2 DXM PROFINET IO Data Model The PROFINET IO data model is based on the typical expandable field device that has a backplane with sl...

Страница 55: ...uration 9 4 Slots and Modules for DXM PROFINET There are ten slots to accommodate the DXM Controller data It is important to note that the module placed in slot 2 corresponds to Port 1 the module plac...

Страница 56: ...gister End Direction 0x4D 0x01 ISDU 190 Byte Status 196 351 442 Bidirectional 196 200 291 0x4E 0x01 ISDU 80 Byte Status 86 351 396 86 200 245 Slot Module Description Slot 1 Banner IO Link Master Info...

Страница 57: ...eering com 2 Launch the Siemens TIA Portal v14 software 3 Click Open existing project 4 Select a project and open it 5 After the project is uploaded click Devices networks Figure 2 Devices and network...

Страница 58: ...ering Corp 9 5 2 Change the Device IP Address Follow these instructions to change the IP address of the DXM device using the Siemens TIA Portal v14 software Use these instructions as a basis if you ar...

Страница 59: ...t 11 Enter the IP address 12 Right click on the device icon and select Online diagnostics Figure 7 Online diagnostics menu and screen STEP RESULT The Online diagnostics windows displays 13 Select Assi...

Страница 60: ...If the DXM is restarted after it was discovered and configured by the PLC the DXM retains the IP address that was assigned to it using the LCD or software until after the PLC discovers the DXM and ass...

Страница 61: ...GHz 5 dBi RP SMA Male Connector Long Range Omni Antennas BWA 9O8 AS Antenna Fiberglass 3 4 Wave 900 MHz 8 dBi N Type Female Connector BWA 2O8 A Antenna Fiberglass 2 4 GHz 8 dBi N Type Female Connector...

Страница 62: ...root directory and subsequent Logging Intervals are appended to the file and are sent at the next Push Interval See Ethernet and Cellular Push Retries on page 49 User Created ScriptBasic Files Users m...

Страница 63: ...processor button until the processor board LED flashes 4 Set DIP switch 4 to the OFF position 5 Cycle power to the DXM Controller 6 Reload the configuration file before resuming normal operation 11 4...

Страница 64: ...adjustments work around configuration solutions or potential new firmware updates 11 5 5 DXM Security The DXM was designed to collect local wireless sensor data local sensor data provide simple contro...

Страница 65: ...ID UE3RM1809 or UE3SX7023EXT Contains IC 7044A RM1809 or 7044A SX7023EXT HVIN RM1809 or 223150 This device complies with Part 15 of the FCC Rules This equipment generates uses and can radiate radio fr...

Страница 66: ...63 When integrated into OEM products fixed antennas require installation preventing end users from replacing them with non approved antennas Antennas not listed in the tables must be tested to comply...

Страница 67: ...ncia prejudicial e n o pode causar interfer ncia em sistemas devidamente autorizados Para maiores informa es consulte o site da ANATEL www gov br anatel pt br Brazil ANATEL 2 4 GHz UE3SX243 03737 22 0...

Страница 68: ...nd wire as short as possible and make all ground connections to a single point ground system to ensure no ground loops are created No surge suppressor can absorb all lightning strikes do not touch the...

Страница 69: ...ngineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSEQUENTI...

Отзывы: