8 Product Support and Maintenance
8.1 Restoring Factory Default Settings for the I/O Base Board
To reset the I/O base board to factory defaults, write to two Modbus registers in the base board. The default slave ID for the
base board is 11.
To reset the DXM I/O base board parameters back to factory defaults:
1. Write a 1 to Modbus register 4152
2. Write a 10 to Modbus register 4151
To reboot (cycle power) the DXM I/O base board:
1. Write a 0 to Modbus register 4152
2. Write a 10 to Modbus register 4151
Table 9: Restoring Factory Defaults for the I/O Base Board
Register
Values
Description
4151
0–255
Reset/restore trigger. This timer is based in 100 millisecond units. Once written, the timer starts to count down to zero. After the
timer expires, the restore factory defaults are applied if register 4152 = 1. If register 4152 is zero, the I/O board is reset.
Default value: 0
1 = 100 milliseconds, 10 = 1 second.
4152
0–1
0 = Reboots (cycles power) to the I/O base board
1 = Restores factory defaults for I/O parameters
8.2 DXM100 Documentation
•
DXM Wireless Controller Sell Sheet, p/n
•
DXM100-B1 Wireless Controller Datasheet, p/n
•
DXM100-B2 Wireless Controller Datasheet, p/n
•
DXM100-Bx Wireless Controller Instruction Manual, p/n
•
DXM100-S1 Modbus Slave Datasheet, p/n
•
DXM100-S2 Modbus Slave Datasheet, p/n
•
DXM100-Sx Modbus Slave Instruction Manual, p/n
•
DXM ScriptBasic Instruction Manual, p/n
•
DXM Controller API Protocol, p/n
•
DXM Controller Configuration Quick Start, p/n
•
SolutionsKit-AG1 Quick Start Guide, p/n
•
DXM Configuration Software v4 (p/n
)
•
DXM Configuration Software v4 Instruction Manual, p/n
•
DXM EDS Configuration filefor Allen-Bradley PLCs, p/n
•
EIP Configuration File for DXM 1xx-BxR1 and R3 models, p/n
•
Banner CDS Web Service Quick Start Guide, p/n
•
Banner CDS Web Service Instruction Manual, p/n
•
Activating a Cellular Modem, p/n
•
Additional technical notes and videos
For more information about the DXM100 family of products, including technical notes, configuration examples, and
ScriptBasic programs, please visit
.
8.3 DXM100 Support Policy
The DXM Wireless Controllers are industrial wireless controllers that facilitate Industrial Internet of Things (IIoT) applications.
As a communications gateway, it interfaces local serial ports, local I/O ports, and local ISM radio devices to the Internet using
either a cellular connection or a wired Ethernet network connection. In a continuing effort to provide the best operation for the
DXM100, stay connected with Banner Engineering Corp to hear about the latest updates through the Banner website. Create
a login today to stay informed of all Banner product releases.
Sure Cross
®
DXM100-Sx Wireless Modbus Slave
www.bannerengineering.com - Tel: + 1 888 373 6767
37