Base Board Input Connection
Modbus Register
Range
Description
3
0–65535
Universal input 3
4
0–65535
Universal input 4
Universal Input Register Ranges
Register Types
Unit
Minimum Value
Maximum Value
Discrete input/output
0
1
Universal input 0 to 10 V
mV
0
10000 *
Universal input 0 to 20 mA
µA
0
20000 *
Universal input temperature (–40 °C to +85 °C)
C or F, signed, in tenths of a degree
–400
850
Universal potentiometer
unsigned
0
65535
* Setting Enable Full Scale to 1 sets the ranges to a linear scale of 0 to 65535.
Base Board Output Connection
Modbus Register
Range
Description
501
0–1
NMOS Output 1
502
0–1
NMOS Output 2
503
0–1
NMOS Output 3
504
0–1
NMOS Output 4
505
0–1
Switched Power 1 (5 V or 16 V)
506
0–1
Switched Power 2 (5 V or 16 V)
507
0–20000
Analog Output 1 default (0-20.000 mA)
0–10000
Analog Output 1 (0-10.000 V)
508
0–20000
Analog Output 2 default (0-20.000 mA)
0–10000
Analog Output 2 (0-10.000 V)
5.2.3 Modbus Configuration Registers for the Universal Inputs
Each input or output on the I/O base board has associated Modbus registers that configure its operation.
Universal Input Parameters Registers
Universal Inputs
1
2
3
4
Enable Full Scale Registers
3303
3323
3343
3363
Temperature °C/°F Registers
3304
3324
3344
3364
Input Type Registers
3306
3326
3346
3366
Threshold Registers
3308
3328
3348
3368
Hysteresis Registers
3309
3329
3349
3369
Enable Rising Registers
4908
4928
4948
4968
Enable Falling Registers
4909
4929
4949
4969
High Register for Counter Registers
4910
4930
4950
4970
Low Register for Counter Registers
4911
4931
4951
4971