Specifications

Sensing Beam

DF-G2: Visible red, 635 nm

DF-G2IR: Infrared, 850 nm

Supply Voltage

10 V to 30 V dc Class 2 (10% maximum ripple)

Power and Current 

Consumption

 (exclusive of load)

Standard display mode: 960 mW, Current 

consumption

 < 40 mA at 24 V dc

ECO display mode: 720 mW, Current 

consumption

 < 30 mA at 24 V dc

Supply 

Protection

 Circuitry

Protected against reverse polarity and transient overvoltages

Delay at Power-Up

500 milliseconds maximum; outputs do not conduct during this 

time

Output 

Configuration

CH1 = IO-Link, Push/pull

CH2 = PNP only output or input

Output 

Rating

100 mA maximum load each output (derate 1 mA per °C above 30° C)

100 mA max total load current for sensor

OFF-state leakage current: < 5 µA PNP at 30 V dc (N.A. push/pull);

ON-state 

saturation

 voltage: < 2 V

Required Overcurrent 

Protection

WARNING: Electrical 

connections

 must be made by

qualified

 personnel in accordance with local and 

national

electrical codes and 

regulations.

Overcurrent 

protection

 is required to be provided by end product 

application

 per

the supplied table.

Overcurrent 

protection

 may be provided with external fusing or via Current

Limiting,

 Class 2 Power Supply.

Supply wiring leads < 24 AWG shall not be spliced.

For 

additional

 product support, go to 

http://www.bannerengineering.com

.

Supply Wiring (AWG)

Required Overcurrent 

Protection

 (Amps)

20

5.0

22

3.0

24

2.0

26

1.0

28

0.8

30

0.5

IO-Link Interface

Supports smart sensor 

profile:

 Yes

Baud rate: 38400 bps

Process data widths: 16 bits

IODD 

files:

 Provides all programming 

options

 of the display, plus 

additional

functionality

Output 

Protection

Protected against output short-circuit, 

continuous

 overload, transient

overvoltages, and false pulse on power-up

Construction

Black ABS/polycarbonate alloy (UL94 V-0 rated) housing, clear polycarbonate

cover

Connections

PVC jacketed 2 m (6.5 

ft)

 4-wire integral cable; or integral 4-pin M8/Pico-

style quick disconnect; or 150 mm (6 inch) cable with a 4-pin M12/Euro-style

quick disconnect; or 150 mm (6 inch) cable with a 4-pin M8/Pico-style quick

disconnect

Adjustments

3-way RUN/PRG/ADJ Mode Switch

2-way CH1/CH2 Switch

3-way +/SET/- Rocker 

Button

Expert-style teaching (Two-Point and Dynamic TEACH, 

Light/Dark/

Window/Calibration

 SET)

Manually adjust 

sensitivity

 (from "+" and "-" rocker 

button

 only)

Response Speed, TEACH 

Selection,

 

Offset

 Percent, Auto

Thresholds, Delays/Timers, Display Readout, Gain 

Selection,

Factory Defaults (from top panel or remote input)

Top panel interface lockout (from remote input only)

Indicators

Red 4-digit Display: Signal Level

Green 4-digit Display: Threshold

(In Program Mode, Red and Green displays are used for programming

menus)

Amber LED: Output 

conducting

Environmental 

Rating

IEC IP50, NEMA 1

Operating

 

Conditions

Temperature: 

10 °C to +55 °C (+14 °F to +131 °F)

Storage Temperature: 

20 °C to +85 °C (

4 °F to +185 °F)

Humidity: 90% at +60 °C maximum 

relative

 humidity (non-condensing)

Certifications

Industrial
Control
Equipment

3TJJ

Response Speed

Description

Response Speed

Repetition

Period

Repeatability

Cross-Talk

Avoidance

Energy 

Efficient

Light Resistance

Maximum Range,

Red22

Maximum Range,

IR85023

Fast

50 us

12 us

12 us

No

No

500

750

Standard

250 us

50 us

50 us

Yes

No

725

1300

Medium Range

500 us

80 us

80 us

Yes

No

900

1600

Long Range

1000 us

165 us

165 us

Yes

No

1100

2100

Long Range (with Immunity)

2000 us

165 us

165 us

Yes

Yes

1100

2100

5.1 Excess Gain Curves

The excess gain curves shown are for the standard red LED and IR850 LED 

emitter

 models.

The data in the charts that is labeled for the Long Range 

application

 apply to both the 1000 µs and 2000 µs response speeds.

22 Excess Gain = 1 at High 

Sensitivity

 

setting;

 opposed mode sensing using PIT46U 

plastic

 

fiber

23 Excess Gain = 1 at High 

Sensitivity

 

setting;

 opposed mode sensing using IT.83.3ST5M6 glass 

fiber

DF-G2 High Speed Expert Dual Display Fiber 

Amplifier

 with Dual Discrete Outputs and IO Link

 

 

24

www.bannerengineering.com - Tel: 763.544.3164

 

Содержание DF-G2 Series

Страница 1: ...High Speed Expert Dual Display Fiber Amplifier with Dual Discrete Outputs and IO Link Instruction Manual Original Instructions 193602 Rev C 21 April 2017 Banner Engineering Corp All rights reserved 1...

Страница 2: ...t 10 3 2 5 Auto Thresholds 10 3 2 6 Delays Timers 11 3 2 7 Sensitivity Selection 11 3 2 8 Display Readout 11 3 2 9 Gain Selection 11 3 2 10 Factory Defaults 11 3 3 Remote Input 11 3 4 Sync Master Slav...

Страница 3: ...ction can cause either an energized or de energized sensor output condition 1 1 Models Model Sensing Beam Color Reference Sensing Range1 Channel 1 Channel 2 Connector2 DF G2 KD 2M Visible Red 1100 mm...

Страница 4: ...put s parameters can be accessed and changed in the interface of the display SET Rocker Button The SET rocker button is a 3 way button The positions are engaged by rocking the button left right The SE...

Страница 5: ...the DIN rail 1 2 Pivot the DF G2 away from the DIN rail and remove it 2 2 2 Installing the Fibers Follow these steps to install glass or plastic fibers 1 Open the dust cover 2 Move the fiber clamp for...

Страница 6: ...RANSMITTER RECEIVER Single core fiber Multi core fiber 2 4 Wiring Diagrams 4 1 3 2 10 30V dc CH1 CH2 PUSH PULL Load Load Figure 2 Channel 1 as a Push Pull discrete output Channel 2 as PNP discrete out...

Страница 7: ...ng changes The SET rocker button is disabled during RUN mode except when using Window SET 3 2 Program Mode Program PRG mode allows the following settings to be programmed in the DF G2 DF G2 High Speed...

Страница 8: ...PLAY LOOP Click SET to enter choice list Click SET display flips 180 Click SET to enter choice list DISPLAY LOOP Click SET to enter choice list DISPLAY LOOP Click SET to enter choice list DISPLAY LOOP...

Страница 9: ...c Click SET to enter choice list DISPLAY LOOP or to set value Click SET or to set value Click SET or to set value Click SET or to set value Click SET or to set value Click SET DISPLAY LOOP DISPLAY LOO...

Страница 10: ...an be programmed to be ON OFF The Auto Thresholds algorithm continuously tracks slow changes in the taught condition s and optimizes the threshold s to provide for reliable sensing For Two Point and D...

Страница 11: ...3 2 8 Display Readout The readout of the digital displays can be programmed for the following options Signal Threshold readout Numeric 1234 or 123P ECO mode Enabled or Disabled ECO mode dims the displ...

Страница 12: ...aves In this mode the sensors alternate taking measurements and the response speed is 2 ms Note Note In this mode all sensors must either be NPN or PNP output models 1 Configure the first sensor as th...

Страница 13: ...Mode switch to ADJ to enter Adjust mode Press to increase press to decrease GREEN display shows the switching threshold value 2 seconds after adjustment the GREEN display will flash 3 times to confirm...

Страница 14: ...nd dark conditions and automatically setting the threshold at the optimum level Sensor positions threshold midway between taught conditions Darkest no signal Most Light saturated signal Output OFF Out...

Страница 15: ...tion Result SET Button Click the SET rocker button TEACH Accepted Displays alternate PASS with Minimum Difference10 Sensor returns to Adjust mode TEACH Not Accepted Displays alternate FAIL with Minimu...

Страница 16: ...tput OFF Output OFF Output ON Figure 10 Window SET Light Operate shown Output ON and OFF conditions can be reversed using the LO DO switch Window SET and Manual Adjust Moves sensing window center valu...

Страница 17: ...Displayed Window Center Displayed Lower Threshold Displayed Figure 11 Upper and Lower Thresholds Light SET Sets a threshold a programmable offset below the presented condition Changes output state on...

Страница 18: ...tion Result SET Button 14 Set Mode switch to ADJ Display Red Signal Level Green Threshold Remote Input 15 No action is required sensor is ready for Light SET method 2 SET Sensing Condition Method Acti...

Страница 19: ...hreshold a programmable offset above the presented condition Threshold position adjusted by Manual Adjust Darkest no signal Most Light saturated signal Output OFF Output ON Condition Presented Figure...

Страница 20: ...on When a condition lighter than the threshold is sensed the output either turns ON or OFF depending on the LO DO setting Sensor positions threshold exactly at the presented condition Threshold positi...

Страница 21: ...abled Manual adjustments are disabled when Auto Thresholds are ON If a manual adjustment is attempted while Auto Thresholds are ON the Green display will flash Percent Minimum Difference after TEACH T...

Страница 22: ...prevent the Auto Thresholds algorithm from optimizing the threshold s State Display Description Corrective Action Threshold Alert Alternates and The threshold s cannot be optimized but the sensor s o...

Страница 23: ...and specifications please visit the web site at http www io link com The IO Link IODD package is contained on the Banner IO Link Device Description Resource CD P N 18491 For the latest IODD files ple...

Страница 24: ...or integral 4 pin M8 Pico style quick disconnect or 150 mm 6 inch cable with a 4 pin M12 Euro style quick disconnect or 150 mm 6 inch cable with a 4 pin M8 Pico style quick disconnect Adjustments 3 wa...

Страница 25: ...st Figure 16 PBT16U Table 2 0 51 mm 0 02 in Diameter Fibers Opposed Mode Diffused Mode 1 10 100 1000 10000 100000 0 1 1 10 100 1000 DISTANCE mm EXCESS GAIN Standard Medium Long Fast Figure 17 PIT26U 1...

Страница 26: ...ium Long Fast Figure 20 PBT46U Table 4 1 52 mm 0 06 in Diameter Fibers Opposed Mode Diffused Mode EXCESS GAIN 1 10 100 1000 10000 DISTANCE mm 1 10 100 1000 10000 100000 1000000 Standard Medium Long Fa...

Страница 27: ...the standard red LED and IR850 LED emitter models The data in the charts that is labeled for the Long Range application apply to both the 1000 s and 2000 s response speeds Table 6 0 25 mm 0 01 in Diam...

Страница 28: ...0 1200 1200 Standard Medium Long Fast Figure 29 PIT46U 0 100 200 300 400 500 DISTANCE mm BEAM WIDTH mm 0 20 20 40 40 60 60 80 80 100 100 Standard Medium Long Fast Figure 30 PBT46U Table 9 1 52 mm 0 06...

Страница 29: ...M WIDTH mm 0 200 200 400 400 600 600 800 800 1000 1000 Standard Medium Long Fast Figure 33 IR850 0 100 200 300 400 500 600 700 DISTANCE mm BEAM WIDTH mm 0 50 50 100 100 150 150 Standard Medium Long Fa...

Страница 30: ...ckets with mounting screws 35 10 Hole center spacing A 16 B 25 4 C 15 2 Hole size A 3 2 B 3 3 C 4 4 6 1 Quick Disconnect Cordsets All measurements are listed in millimeters unless noted otherwise 4 Pi...

Страница 31: ...yp M8 x 1 PKW4M 5 5 m 16 4 ft PKW4M 9 9 m 29 5 ft 4 Pin Snap on M8 Pico Style Cordsets Model Length Style Dimensions Pinout Female PKG4 2 2 m 6 6 ft Straight 9 0 32 Typ 4 3 1 2 1 Brown 2 White 3 Blue...

Страница 32: ...PENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRAN...

Отзывы: