Asset Monitoring Gateway With SNAP ID Instruction Manual
22
Configure the HMI to Push Information to the Cloud
IMPORTANT:
Always create a new gateway with the BannerCDS system and commission applicable sen
sors before turning Cloud Push Enable to Yes. Failure to do so can result in long wait times for the web
site to autodetect.
Enter the AMG serial number found in the
Utilities
›
DXM Details
screen.
6.
Click
Save.
7.
On the HMI: Go to DXM Utilities ›
DXM Configuration
to enable cloud pushing.
1.
Change the
Threshold Filter
to a number greater than 0 (3 is recommended).
2.
Verify your device's
Push Communication Mode
is accurate to your model.
3.
Toggle
Cloud Push Enable
to
Yes.
HMI Utilities screen
4.
Change the
Cloud Push Interval
to a desired time.
The default push interval is 600 seconds (10 minutes).
5.
Press
Save
and confirm. The AMG pushes immediately upon confirmation. The user can track the HTTP data within
the
DXM Utilities
›
DXM HTTP Status
screen.
6.