 General safety guidelines

2.6 Operation

2.6.1 Protection against contact with electrical parts

In order to operate programmable logic controllers, operating and monitoring devices and uninterruptible power

supplies, it is necessary for certain components to carry dangerous voltages over 42 VDC. Touching one of these

components can result in a life-threatening electric shock. There is a risk of death, serious injury or damage to

property.
Before switching on programmable logic controllers, operating and monitoring devices and uninterruptible power

supplies, it must be ensured that the housing is properly connected to ground potential (PE rail). Ground connec-

tions must also be made if the operating and monitoring device and uninterruptible power supply are only connect-

ed for testing purposes or only operated for a short time!
Before switching on, live parts must be securely covered. All covers must be kept closed during operation.

2.6.2 Ambient conditions - Dust, moisture, aggressive gases

The use of operating and monitoring devices (e.g. industrial PCs, Power Panels, Mobile Panels) and uninterruptible

power supplies in dusty environments must be avoided. This can otherwise result in dust deposits that affect the

functionality of the device, especially in systems with active cooling (fans), which may no longer ensure sufficient

cooling.
The presence of aggressive gases in the environment can also result in malfunctions. In combination with high

temperature and relative humidity, aggressive gases – for example with sulfur, nitrogen and chlorine components

– trigger chemical processes that can very quickly impair or damage electronic components. Blackened copper

surfaces and cable ends in existing installations are indicators of aggressive gases.
When operated in rooms with dust and condensation that can endanger functionality, operating and monitoring

devices such as Automation Panels or Power Panels are protected on the front against the ingress of dust and

moisture when installed correctly (e.g. cutout installation). The back of all devices must be protected against the

ingress of dust and moisture, however, or the dust deposits must be removed at suitable intervals.

2.6.3 Programs, viruses and malicious programs

Any data exchange or installation of software using data storage media (e.g. floppy disk, CD-ROM, USB flash

drive) or via networks or the Internet poses a potential threat to the system. It is the direct responsibility of the user

to avert these dangers and to take appropriate measures such as virus protection programs and firewalls to protect

against them and to use only software from trustworthy sources.

SDL3 Converter User's manual V 2.01

9

Содержание SDL3

Страница 1: ...SDL3 Converter User s manual Version 2 01 November 2022 Order no MASDL3CON ENG Translation of the original documentation...

Страница 2: ...hardware designations and brand names of the respective companies used in this document are subject to general trademark brand or patent protection Hardware and software from third party suppliers re...

Страница 3: ...s 12 3 3 1 SDL3 operation 12 3 3 1 1 SDL3 operation with SDL3 Converter via SDL 12 3 3 1 2 SDL3 operation with SDL3 Converter via DVI 14 3 3 2 General limitations characteristics 14 3 4 Design Configu...

Страница 4: ...ons 37 9 1 1 CE marking 37 9 1 2 EMC Directive 37 9 2 Certifications 38 9 2 1 UL certification 38 9 2 2 EAC 38 9 2 3 UKCA 38 10 Accessories 39 10 1 General accessories 39 10 1 1 Accessories Order data...

Страница 5: ...14 12 17 First version 1 Editorial corrections are not listed 1 2 Information about this document This document is not intended for end customers The safety guidelines required for end customers must...

Страница 6: ...in millimeters Unless otherwise specified the following general tolerances apply Nominal dimension range General tolerance per DIN ISO 2768 medium Up to 6 mm 0 1 mm Over 6 to 30 mm 0 2 mm Over 30 to...

Страница 7: ...that could result in death injury serious physical harm or other loss without the assurance of exceptionally stringent safety precautions B R products are explicitly not intended for use in the follo...

Страница 8: ...e safety measures that apply to industrial controllers protection by protective equip ment such as emergency stops must be observed in accordance with applicable national and international regu lation...

Страница 9: ...f the device especially in systems with active cooling fans which may no longer ensure sufficient cooling The presence of aggressive gases in the environment can also result in malfunctions In combina...

Страница 10: ...entation of the network e g separation of the IT network from the control network1 Use of firewalls Use of authentication mechanisms Encryption of data Use of anti malware software Before B R releases...

Страница 11: ...ers mm 3 2 SDL3 Converter for Automation PCs Smart Display Link 3 offers even more advantages when used together with an external converter For example SDL3 can be used to connect Automa tion Panels t...

Страница 12: ...R industrial PC is equipped with an SDL3 transmitter then an additional SDL3 graphics line can also be implemented The brightness of the display can be set via the B R ADI Control Center Operation wit...

Страница 13: ...rated in the SDL transfer and transferred over this distance Automation Panel with SDL3 receiver B R industrial PC SDL cable SDL3 cable SDL3 Converter Power supply SELV PELV Availability of interfaces...

Страница 14: ...2 0 Power supply Grounding Maximum cable length for SDL3 100 m Maximum cable length for DVI and USB 5 m Requirements Automation Panel with SDL3 receiver Industrial PC with DVI interface SDL3 Converter...

Страница 15: ...0 SDL cables with 45 connector 5CASDL 0018 01 5CASDL 0050 01 5CASDL 0100 01 SDL flex cables 5CASDL 0018 03 5CASDL 0050 03 5CASDL 0100 03 DVI cables Select 12 5CADVI 0018 00 5CADVI 0050 00 USB cables S...

Страница 16: ...15 m FT50 including Power over Eth ernet 5CASD3 0200 00 SDL3 SDL4 FT50 cable 20 m FT50 including Power over Eth ernet 5CASD3 0300 00 SDL3 SDL4 FT50 cable 30 m FT50 including Power over Eth ernet 5CASD...

Страница 17: ...ature Operation 0 to 55 C 2 Storage 20 to 60 C Transport 20 to 60 C Relative humidity Operation 5 to 90 non condensing Storage 5 to 95 non condensing Transport 5 to 95 non condensing Vibration 3 Opera...

Страница 18: ...ation All specifications in dimension diagrams and associated tables are in millimeters mm 2D and 3D diagrams DXF and STEP formats can be downloaded from the B R website www br automation com 100 40 8...

Страница 19: ...the purpose of clear differentiation The numbering used by the operating system may deviate however View A View B A B Legend 1 LED status indicators on page 22 4 24 VDC power supply on page 20 2 SDL...

Страница 20: ...n 3 pin Male Electrical properties Nominal voltage 24 VDC 25 SELV1 Nominal current Max 0 2 A Overvoltage category per EN 61131 2 II Galvanic isolation Yes 1 EN 60950 requirements must be observed 3 5...

Страница 21: ...en segment length and maximum resolution depending on the SDL cable Resolution SDL cable Segment length m VGA 640 x 480 SVGA 800 x 600 XGA 1024 x 768 HD 1366 x 768 SXGA 1280 x 1024 UXGA 1600 x 1200 FH...

Страница 22: ...communication Faulty or incomplete firmware up grade Blinking No active SDL communication Status Yellow Blinking On 50 brightness Off No active SDL communication Faulty or incomplete firmware up grade...

Страница 23: ...5ACCRHMI 0011 000 Strain relief USB For APC2100 APC2200 For SDL3 Converter SDL4 Converter 41 Converter 5COSD3 1000 00 SDL SDL3 Converter 16 Other 5ACCRHMI 0006 000 HMI installation tool for control ca...

Страница 24: ...of the complete system If additional space is required for operating or servicing the device or using accessories e g cable strain relief clips this must be taken into account during installation Leg...

Страница 25: ...from the device and installing or removing any accessories hardware or cables Remove the power cable from the device and from the power supply All covers and components accessories hardware and cable...

Страница 26: ...n environmental conditions or rapid climatic changes For im proved acclimatization and to avoid damage the device must be slowly adapted to the room temper ature When transporting at low temperatures...

Страница 27: ...ws the system to be installed on a top hat rail TS35 that corresponds to the EN 50022 standard 35 1 7 5 5 2 1 Procedure 1 Attach the SDL3 Converter in the desired position to the top hat rail 1 and pr...

Страница 28: ...following figure and secured with the supplied locating screws M3 max tightening torque 0 5 Nm The cable strain relief clip is only permitted to be installed at the intended location on the device 2...

Страница 29: ...pply unit 5 4 1 1 Wiring Caution The pinout of the power supply interface must be observed The DC power cable must be implemented with a wire cross section of 0 75 mm2 to 1 5 mm2 and wire end sleeves...

Страница 30: ...ecting the power cable it must be checked whether it has been disconnected from the voltage source e g power supply unit 1 Carry out electrostatic discharge on the housing or at the ground connection...

Страница 31: ...mbol The following points must be observed to ensure that electrical interference is safely diverted Connect the device to the central grounding point e g the control cabinet or the system using the s...

Страница 32: ...lling cables the bend radius specification must be observed For this specification see the technical data of the respective cable The maximum tightening torque of the locating screws is 0 5 Nm 2 2 1 1...

Страница 33: ...L3 Converter 5 6 1 Procedure 1 Pull the SDL3 Converter downwards 1 and slightly in the opposite direction away from the top hat rail 2 This releases the locking mechanism for the top hat rail installa...

Страница 34: ...ground connection Before installing additional hardware the device must have been started up Caution Before the device is started up it must be gradually adapted to room temperature Exposure to direct...

Страница 35: ...rmware an APC3100 APC2200 APC2100 APC910 or PPC3100 or PPC900 with compatible MTCX firmware must be connected in addition to an Automation Panel with an SDL3 link module A current firmware upgrade can...

Страница 36: ...nts and replacement parts Danger Unauthorized opening or repair of a device may result in personal injury and or serious damage to property Repairs are therefore only permitted to be carried out by au...

Страница 37: ...U and are designed for industrial applications EN 61131 2 2007 Programmable controllers Part 2 Equipment requirements and tests EN 61000 6 2 2005 Electromagnetic compatibility EMC Part 6 2 Generic sta...

Страница 38: ...ories and listed as indus trial control equipment The mark is valid for the USA and Canada and simplifies the certification of your machines and systems in this economic area Underwriters Laboratories...

Страница 39: ...PC link modules and converters Grounding clip Cable strain relief clip for USB see Cable strain relief clip on page 41 10 1 1 Accessories Order data Material number Description 5ACCRHMI 0000 000 REP H...

Страница 40: ...ibration 0 7 g EMC bridge and open deck EAC Yes Terminal block Note Protected against vibration by the screw flange Nominal data per UL Number of pins 3 female Type of terminal block Screw clamp termi...

Страница 41: ...er data Order number Short description Figure Accessories 5ACCRHMI 0011 000 Strain relief USB For APC2100 APC2200 For SDL3 Convert er SDL4 Converter 10 4 1 3 Technical data Order number 5ACCRHMI 0011...

Страница 42: ...can be recycled in an environmentally friendly manner it is necessary to separate out the different materials Component Disposal Programmable logic controllers Operating and monitoring devices Uninte...

Отзывы: