Installation • Installation
154
Panel PC 800 User's Manual V1.30
1.4 Spacing for air circulation
In order to guarantee sufficient air circulation, allow the specified amount of space above, below, to the side and
behind the Panel PC 800 devices. The minimum specified spacing is indicated in the following diagram. This applies
to all Panel PC 800 variants.
At least
10 mm Abstand
At least
10 mm Abstand
Air outlet
At
le
as
t
10
0
m
m
A
bs
ta
nd
Air inlet
At least
50 mm Abstand
At
le
as
t
10
0
m
m
A
bs
ta
nd
Side view
Rear view
Figure 70: Spacing for air circulation
Information:
The spacing specifications for air circulation are based on the worst-case scenario for operation at the
maximum specified ambient temperature (see "Temperature specifications" in the chapter "Technical
data").
If the spacing specifications for air circulation cannot be adhered to, then the maximum specified tem-
peratures for the temperature sensors (see "Temperature sensor positions" in the chapter "Technical
data") must be monitored by the user and appropriate measures taken if they are exceeded.