3.1.3 Mounting an Automation Panel 1000 with retaining clips
The Panel PC 2100 with AP1000 panel is installed in the cutout using retaining clips. The number of retaining clips
depends on the panel.
The following Automation Panel 1000 panels are mounted using retaining clips:
•
5AP1120.0573-000
•
5AP1151.0573-000
•
5AP1120.0702-000
•
5AP1130.0702-000
•
5AP1120.101E-000
•
5AP1130.101E-000
•
5AP1120.1043-000
•
5AP1180.1043-000
•
5AP1120.121E-000
•
5AP1130.121E-000
•
5AP1120.156B-000
•
5AP1130.156C-000
•
5AP1130.185C-000
The thickness of the wall or control cabinet plate must be at least 1 mm and is not permitted to exceed 6 mm.
A 2.5 mm hex screwdriver is needed to tighten and remove the screw on the retaining clips. The maximum tightening
torque of the retaining clips is 1 Nm.
Devices must be installed on a flat, clean and burr-free surface; tightening screws on an uneven area can result
in damage to the display or the ingress of dust and water.
Procedure
1. Check whether the included mounting screws are screwed into the retaining clips. If not, then the mounting
screws must be screwed into the retaining clips with a 2.5 mm hex key screwdriver. The mounting screws
are permitted to be screwed in far enough that they no longer protrude above the retaining clip.
Retaining clip
Mounting screws
Figure 115: Preparing the retaining clips
2. Insert the device into the front of the prepared, burr-free and flat installation cutout. For the dimensions of the
cutout, see
Fig. X "AP1000 panels with retaining clips - Installation diagrams" on page
.
3. Install the retaining clips on the device. This is done by inserting the clips into the openings on the sides of
the device (indicated by the orange circles). The number of retaining clips may vary depending on the panel.
For the exact number, see
Fig. X "AP1000 panels with retaining clips - Installation diagrams" on page
.