Programming guidelines
226
ACOPOSinverter P84 User's Manual 2.10
2.8.11.11.4.1 Brake control logic expert parameters
Code
Name/Description
Factory settings
brH0
[BRH_b0]
0
Selection of the brake restart sequence if a run command is repeated while the brake is engaging.
0
[0]
(0)
: The brake engaging/brake release sequence is executed completely.
1
[1]
(1)
: The brake is immediately reopened.
Use in the open and closed-loop control
•
A run command may be requested during the brake release phase. Whether the sequence for the new brake engaging is executed,
depends on the value selected for
[BRH b0]
(brH0)
.
Movement command
Frequency
Relay or
Logic output
Frequency
bEn
Relay or
Logic output
[BRH_b0]
(brH0)
= 0
[BRH_b0]
(brH0)
= 1
Note:
If a run command is requested during the "ttr" phase, the complete brake control sequence is initialized.
brH1
[BRH b1]
0
Deactivation of the brake contact fault in the set mode.
0
[0]
(0)
: The "brake feedback" fault is active in steady state (fault if the contact is open during operation). The brake contact fault brF is monitored
in all operating phases.
1
[1]
(1)
: The "brake feedback" fault is not active in steady state. The brake contact error brF is only monitored during brake release and engaging
phases.
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...