Programming guidelines
310
ACOPOSinverter P84 User's Manual 2.10
[MODBUS HMI] (Md2-), [MODBUS NETWORK] (MdI-) and [CANopen] (CnO-)
Code
Name/Description
Factory settings
Md2-
[MODBUS HMI]
Communication with the graphic display terminal.
tbr2
[Baud rate HMI]
19.2 kbit/s
9.6 or 19.2 kbit/s on the integrated display terminal.
9600 or 19200 baud on the graphic display terminal.
The graphic display terminal only works if
[Baud rate HMI]
(tbr2)
= 19200 Baud (19.2 kbit/s).
To take changes in the assignment of
[Baud rate HMI]
(tbr2)
into account, you must:
•
When using the graphic display terminal, confirm the changes in a confirmation window
•
When using the integrated display terminal, press the ENT key for 2 seconds
tFO2
[Format HMI]
8E1
Read-only parameter, cannot be modified.
Md1-
[MODBUS NETWORK]
Not applicable
CnO-
[CANopen com.]
AdCO
[CANopen address]
OFF
OFF to 127
bdCO
[CANopen bit rate]
125 kbit/s
50 - 125 - 250 - 500 kbit/s - 1 Mbit/s
ErCO
[Error code]
Read-only parameter, cannot be modified.
[COMM CARD] and [FORCED LOCAL] (LCF-)
Code
Name/Description
Factory settings
-
[COMMUNICATION CARD]
You can find additional information in the documentation for the specific card.
LCF-
[Forced local]
FLO
[Forced local]
[No]
(nO)
nO
[No]
(nO)
: Function not active
LI1
[LI1]
(LI1)
to
[LI6]
(LI6)
-
LI6
The on-site operation is active in state 1 of the input.
[FORCED LOCAL]
(FLO)
is forced to
[No]
(nO)
if
[Profil]
(CHCF)
=
[I/O profile]
(IO)
.
FLOC
[Forced local Ref.]
[No]
(nO)
nO
[No]
(nO)
: Not assigned (control via the terminals with zero reference).
AI1
[AI1]
(AI1)
: Analog input
AI2
[AI2]
(AI2)
: Analog input
LCC
[HMI]
(LCC)
: Assignment of the reference and the control to the graphic display terminal.
PG
Reference:
[HMI Freq Ref.]
(LFr)
Command: RUN/STOP FWD/REV buttons.
[Encoder]
(PG)
: Encoder input if encoder card has been inserted
If the reference is assigned to an analog input or
[Encoder]
(PG)
, the command is automatically assigned to the terminals as well as the logic inputs
FLOt
[Time-out forc. local]
10 s
0.1 to 30 s
This parameter can be activated if
[FORCED LOCAL]
(FLO)
is not equal to
[No]
(nO)
.
Time delay before communication monitoring is resumed on leaving forced local mode.
Содержание 8I84T200037.01P-1
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...