Technical data • Individual components
Chapter 2
Technical data
Power Panel 500 User's Manual V 1.00
121
Product ID
5PP5IF.FPLM-00
Relative humidity
Operation
5 to 90%, non-condensing
Storage
5 to 95%, non-condensing
Transport
5 to 95%, non-condensing
Table 55: 5PP5IF.FPLM-00 - Technical data
3.4.3.3.1 POWERLINK
POWERLINK Interface Board 2 connections
Cabling
S/STP (Cat5e)
Cable length
max. 100 m (min. Cat5e)
Speed LED
On
Off
Green / red
see Status / Error LED
Link LED
On
Off
Yellow
Link (POWER-
LINK network con-
nection available)
Activity (blinking - data
transfer in progress)
Table 56: POWERLINK Interface Board 2port connection
3.4.3.3.2 Status / Error LED
The status/error LED is a green/red LED.
Red - error
Description
On
The POWERLINK interface has encountered an error (failed Ethernet frames, increased number
of collisions on the network, etc.).
Table 57: Status / Error LED as error LED - POWERLINK operating mode
Green - status
Description
Off
NOT_ACTIVE
Managing Node (MN)
The bus is monitored for POWERLINK frames. If a frame is not received within the configured
time window (timeout), the interface goes directly into PRE_OPERATIONAL_1 status (single
flash).
If, however, POWERLINK communication is detected before this time passes, the interface
goes directly into the BASIC_ETHERNET status (flickering).
Controlled Node (CN)
The bus is monitored for POWERLINK frames. If a frame is not received within the configured
time window (timeout), the interface goes directly into BASIC_ETHERNET status (flickering).
If, however, POWERLINK communication is detected during this time, the interface goes directly
into the PRE_OPERATIONAL_1 status (single flash).
Green flickering (approx. 10 Hz)
BASIC_ETHERNET
The interface is in BASIC_ETHERNET status, and is operated purely as an Ethernet TCP/IP in-
terface.
Managing Node (MN)
This status can only be changed by resetting the interface.
Controlled Node (CN)
If POWERLINK communication is detected while in this status, the interface goes into the
PRE_OPERATIONAL_1 state (single flash).
Table 58: Status/Error LED as status LED - POWERLINK operating mode
Содержание 5PP551.0573-00
Страница 2: ...2 Power Panel 500 User s Manual V 1 00...
Страница 4: ...4 Power Panel 500 User s Manual V 1 00...
Страница 5: ...Power Panel 500 User s Manual V 1 00 5 Appendix A...
Страница 40: ...Technical data Entire device 40 Power Panel 500 User s Manual V 1 00 2 4 11 Mode Node switches...
Страница 210: ...Accessories CompactFlash cards 210 Power Panel 500 User s Manual V 1 00 3 3 6 Benchmark...
Страница 253: ...Power Panel 500 User s Manual V 1 00 253...